1500 North Belcher Road, Clearwater, FL 33765 • Tel (727) 447-6140 • Fax (727) 442-5699 • [email protected]
Turbine Flow Meter Manual 05/13 - 0721-1 / 13518
Page 45
1500 North Belcher Road, Clearwater, FL 33765 • Tel (727) 447-6140 • Fax (727) 442-4599
www.onicon.com • [email protected]
0543-2
07-12
For Use With Kits: INSTL10, INSTL11, INSTL12, INSTL13,
INSTL14, INSTL15, INSTL16, INSTL17
Pipe saddle types vary by application.
Important Note
ONICON provides pipe saddles to facilitate the installation of our flow meters. Separate
installation instructions accompany the saddle. Please follow these instructions when installing
the saddle. Pay particular attention to bolt torque specifications and temperature/pressure limits.
Installation Hardware Instructions
Standard Installation Kit for Applications Requiring Pipe Saddles
For F-1100, F-1200 & FB-1200 Series Insertion Turbine Flow Meters
This kit must be installed prior to filling the system, or into a section of pipe that is isolated from
pressure and flow. Once installed, this kit allows for insertion and removal of the flow meter without
a system shutdown.
Directions
:
1. Identify an appropriate location for the flow meter
(see pages 2-4).
2. Clamp the saddle onto the pipe; refer to
manufacturer’s instructions.
3. Drill a 1” (minimum) access hole in the pipe,
centered in the outlet.
4. Install the reducer, close nipple and ball valve as
shown below. Use a paste type thread sealant.
DO NOT use Teflon
®
tape.
5. Flush and fill the system prior to installing the
meter.
NOTE: Before installing the flow meter, read the entire installation manual.
Important Note
ONICON insertion flow meters
are precision measuring devices
that must be installed according to
the instructions contained in this
document in order to maintain their
accuracy and reliability. Failure to
follow these instructions will result
in erratic operation and reduced
accuracy.
*
*
Bushing may not be
required in all cases.
(see Sections 3.1 and 3.2).