One Lux ONE-SENSE EXO Скачать руководство пользователя страница 1

 

Issue C

                           

                                                                           

         

 

 

MICROWAVE MOTION SENSOR USER GUIDE 

Model  No.:  OS/  EXO

 

 

     

Model: OS EXO                                                            Dimensions (mm)

       

 

Technical Specifications 

Input voltage 

 

220/240Vac 50Hz 

   

 

TUV     

Rated load 

 

400W(Inductive load), 800W(Resistive load) 

Detection area 

 

0.5m ~ 8m, adjustable.   

Hold time 

 

10sec / 30sec / 90sec / 3min / 20min / 30min. 

Daylight sensor 

 

5 lux / 10 lux / 30 lux / 50 lux / Disable. 

(Typical)

 

Sensor principle 

 

Microwave motion detector 

Microwave frequency 

 

5.8GHz±75Hz, ISM wave band 

Transmitting power 

 

<0.5mW (1% of transmitting power for cell phone) 

Detection range 

 

Max. 

(Ф x h): 16m x 6m.   

Detection angle 

 

150° (Wall installation) 

360° (Ceiling installation) 

Motion detection 

 

0.5 ~ 3m/s.   

Operating temperature 

 

-20

°C 

- 60

°C

 

IP rating 

 

IP20 

 

General Guidelines for Installation 

 

1,  Specifications  for  detection  area,  detection  range  and  daylight  sensor  levels  are  typical,  so 

suitability should be determined for sensitive applications. 

2, The Motion sensor should be installed by a qualified electrician. Ensure  the electricity supply is 

switched off before installing or servicing the product. 

3,  The  sensor  should  not  be  modified  in  any  way.  Any  modifications  mode  to  this  product  will 

immediately invalidate any warranties issued. 

4, The company does not accept responsibility for any consequences resulting from unauthorized 

modification of the product. 

5, The sensor should be connected to a stable power supply of 220/240Vac 50Hz. 
6, Microwaves cannot pass through metal or brick walls if thicker than 20cm. They will pass through 

thinner walls but there will be some attenuation. 

7,  Installation  inside  a  glass  or  plastic  housing  will  result  in  a  reduction  of  detection  sensitivity. 

Expect a reduction of approximately 20% for every 3mm of thickness.

 

 

Installation & Wiring 

The sensor is designed for installation at 1~6m in height.   

Suggested mounting height:   

1~1.8m (Wall mounting)   

2.5~6m (Ceiling mounting)     

 

 

 

Note: L(BLACK) , N(BLUE) ,L

’(BROWN) 

 