2-1
Specifications
2-1-1
General Specifications
This section provides the general specifications of the High-speed Analog Input Units.
Item
Specification
Enclosure
Mounted in a panel
Grounding methods
Ground of 100 Ω or less
Operating en-
vironment
Ambient operating temper-
ature
0 to 55
°
C
Ambient operating humidi-
ty
10% to 95% (with no condensation or icing)
Atmosphere
Must be free from corrosive gases.
Ambient storage tempera-
ture
-25 to 70
°
C (with no condensation or icing)
Altitude
2,000 m max.
Pollution degree
2 or less: Conforms to JIS B 3502 and IEC 61131-2.
Noise immunity
Conforms to IEC 61000-4-4, 2 kV (power supply line)
Overvoltage category
Category II: Conforms to JIS B 3502 and IEC 61131-2.
EMC immunity level
Zone B
Vibration resistance
Conforms to IEC 60068-2-6.
5 to 8.4 Hz with amplitude of 3.5 mm,
8.4 to 150 Hz, acceleration of 9.8 m/s
2
100 min each in X, Y, and Z directions (10 sweeps of 10 min
each = 100 min total)
Shock resistance
Conforms to IEC 60068-2-27, 147 m/s
2
, 3 times each in X, Y,
and Z directions
Insulation resistance
Refer to the individual specifications of NX Units.
Dielectric strength
Refer to the individual specifications of NX Units.
Applicable standards
cULus: Listed (UL61010-2-201), ANSI/ISA 12.12.01, EU: EN
61131-2, RCM, KC (KC Registration), and EAC
Note 1. The specifications of insulation resistance and dielectric strength vary with NX Unit Models.
Note 2. Refer to the OMRON website (www.ia.omron.com) or ask your OMRON representative for the most re-
cent applicable standards for each model.
2-1-2
Individual Specifications
on page A - 2 for the individual specifications of the High-speed Analog
Input Units.
2 Specifications and Operating Procedures
2 - 2
NX-series Analog I/O Units User’s Manual for High-speed Analog Input Units (W592)
Содержание Sysmac NX-series
Страница 4: ...Introduction 2 NX series Analog I O Units User s Manual for High speed Analog Input Units W592...
Страница 42: ...Sections in this Manual 40 NX series Analog I O Units User s Manual for High speed Analog Input Units W592...
Страница 100: ...4 Installation and Wiring 4 32 NX series Analog I O Units User s Manual for High speed Analog Input Units W592...
Страница 142: ...7 I O Data and List of Settings 7 24 NX series Analog I O Units User s Manual for High speed Analog Input Units W592...
Страница 238: ...10 Inspection and Maintenance 10 6 NX series Analog I O Units User s Manual for High speed Analog Input Units W592...
Страница 300: ...Appendices A 62 NX series Analog I O Units User s Manual for High speed Analog Input Units W592...
Страница 301: ...I Index I 1 NX series Analog I O Units User s Manual for High speed Analog Input Units W592 I...
Страница 303: ...W Wiring Terminal 4 7 Index I 3 NX series Analog I O Units User s Manual for High speed Analog Input Units W592 I...
Страница 304: ......
Страница 305: ......