Event name
I/O Allocation Setting Error
Event code
30070000 hex
Meaning
I/O allocations are not set correctly.
Source
Depends on where the Support
Software is connected and the
system configuration.
Source details
NX Unit
Detection tim-
ing
Continuously
Error attrib-
utes
Level
Minor fault
Log category
System
Recovery
For the NX bus of CPU Units
Restart the NX bus.
For Communications Coupler Units
Restart the Slave Terminal.
Effects
User program
Continues.
Operation
I/O refreshing for the NX Unit stops.
System-de-
fined varia-
bles
Variable
Data type
Name
None
---
---
Cause and
correction
Assumed cause
Correction
Prevention
For the NX bus of CPU Units
I/O Entry that matches the follow-
ing setting items of unit operation
settings has not been set in I/O
allocation settings.
•
Ch
£
Number of Samplings
Setting
•
Ch
£
Enable/Disable
After you set the Ch
£
Number of
Samplings and Ch
£
Enable/ Dis-
able settings, update the I/O En-
try. By updating I/O Entry in the
I/O Allocation Settings Window
on the Support Software, neces-
sary I/O Entry is automatically
set. After this setting, download
the Unit operation settings and
the I/O allocation settings again.
After you set the Ch
£
Number of
Samplings and Ch
£
Enable/ Dis-
able settings, update the I/O En-
try. By updating I/O Entry in the
I/O Allocation Settings Window
on the Support Software, neces-
sary I/O Entry is automatically
set.
For Communications Coupler Units
I/O Entry that matches the follow-
ing setting items of unit operation
settings has not been set in I/O
allocation settings.
•
Ch
£
Number of Samplings
Setting
•
Ch
£
Enable/Disable
After you set the Ch
£
Number of
Samplings and Ch
£
Enable/ Dis-
able settings, update the I/O En-
try. By updating I/O Entry in the
I/O Allocation Settings Window
on the Support Software, neces-
sary I/O Entry is automatically
set. After this setting, download
the Unit operation settings and
the I/O allocation settings again.
After you set the Ch
£
Number of
Samplings and Ch
£
Enable/ Dis-
able settings, update the I/O En-
try. By updating I/O Entry in the
I/O Allocation Settings Window
on the Support Software, neces-
sary I/O Entry is automatically
set.
The Number of Samplings Set-
ting was set to other than 1 and
the Enable Distributed Clock set-
ting for the EtherCAT Coupler
Unit was set to Disabled.
Set the Enable Distributed Clock
setting for the EtherCAT Coupler
Unit to Enabled (DC for synchro-
nization) or Enabled (DC with pri-
ority in cycle time) and then
download the Slave Terminal pa-
rameter settings again.
For the High-speed Analog Input
Units, synchronous I/O refresh-
ing is always used. Therefore,
set the Enable Distributed Clock
setting for the EtherCAT Coupler
Unit to Enabled (DC for synchro-
nization) or Enabled (DC with pri-
ority in cycle time).
Attached in-
formation
None
Precautions/
Remarks
None
9 Troubleshooting
9 - 18
NX-series Analog I/O Units User’s Manual for High-speed Analog Input Units (W592)
Содержание Sysmac NX-series
Страница 4: ...Introduction 2 NX series Analog I O Units User s Manual for High speed Analog Input Units W592...
Страница 42: ...Sections in this Manual 40 NX series Analog I O Units User s Manual for High speed Analog Input Units W592...
Страница 100: ...4 Installation and Wiring 4 32 NX series Analog I O Units User s Manual for High speed Analog Input Units W592...
Страница 142: ...7 I O Data and List of Settings 7 24 NX series Analog I O Units User s Manual for High speed Analog Input Units W592...
Страница 238: ...10 Inspection and Maintenance 10 6 NX series Analog I O Units User s Manual for High speed Analog Input Units W592...
Страница 300: ...Appendices A 62 NX series Analog I O Units User s Manual for High speed Analog Input Units W592...
Страница 301: ...I Index I 1 NX series Analog I O Units User s Manual for High speed Analog Input Units W592 I...
Страница 303: ...W Wiring Terminal 4 7 Index I 3 NX series Analog I O Units User s Manual for High speed Analog Input Units W592 I...
Страница 304: ......
Страница 305: ......