Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
:
:
+18
1st byte of Analog Input Value 20 in Ch
£
Analog Input Value 11-20
+19
2nd byte of Analog Input Value 20 in Ch
£
Analog Input Value 11-20
The bit configuration of the Ch
£
Analog Input Value 991-1000 (ARRAY[0..9] OF INT) is given in the
following table.
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
1st byte of Analog Input Value 991 in Ch
£
Analog Input Value 991-1000
+1
2nd byte of Analog Input Value 991 in Ch
£
Analog Input Value 991-1000
+2
1st byte of Analog Input Value 992 in Ch
£
Analog Input Value 991-1000
+3
2nd byte of Analog Input Value 992 in Ch
£
Analog Input Value 991-1000
+4
1st byte of Analog Input Value 993 in Ch
£
Analog Input Value 991-1000
+5
2nd byte of Analog Input Value 993 in Ch
£
Analog Input Value 991-1000
:
:
+18
1st byte of Analog Input Value 1000 in Ch
£
Analog Input Value 991-1000
+19
2nd byte of Analog Input Value 1000 in Ch
£
Analog Input Value 991-1000
Ch
£
Operation Command
This is aggregated Operation Command data that the High-speed Analog Input Units use to execute
functions such as Digital Low-pass Filter Disable and Zero Set Execution.
Data name
Data type
Default val-
ue
I/O port name
Unit
Index
number
(hex)
Subindex
number
(hex)
Ch1 Operation Com-
mand
WORD
0000 hex
Ch1 Operation Com-
mand
---
7000
01
Ch2 Operation Com-
mand
WORD
0000 hex
Ch2 Operation Com-
mand
---
7001
01
Ch3 Operation Com-
mand
WORD
0000 hex
Ch3 Operation Com-
mand
---
7002
01
Ch4 Operation Com-
mand
WORD
0000 hex
Ch4 Operation Com-
mand
---
7003
01
The bit configuration and the description of each bit for the Ch
£
Operation Command are given in the
following table.
Bit
Data name
Description
Data
type
I/O port name
0
Ch
£
Digital Low-
pass Filter Disa-
ble
1: Disables the digital low-pass filter.
0: Enables the digital low-pass filter.
If the low-pass filter frequency is set to 0 in the Unit op-
eration settings, the digital low-pass filter will not be en-
abled even if you set this bit to 0.
BOOL
Ch
£
Digital
Low-pass Filter
Disable
7 I/O Data and List of Settings
7 - 11
NX-series Analog I/O Units User’s Manual for High-speed Analog Input Units (W592)
7-1 Specifications of I/O Data
7
7-1-2
Data Details
Содержание Sysmac NX-series
Страница 4: ...Introduction 2 NX series Analog I O Units User s Manual for High speed Analog Input Units W592...
Страница 42: ...Sections in this Manual 40 NX series Analog I O Units User s Manual for High speed Analog Input Units W592...
Страница 100: ...4 Installation and Wiring 4 32 NX series Analog I O Units User s Manual for High speed Analog Input Units W592...
Страница 142: ...7 I O Data and List of Settings 7 24 NX series Analog I O Units User s Manual for High speed Analog Input Units W592...
Страница 238: ...10 Inspection and Maintenance 10 6 NX series Analog I O Units User s Manual for High speed Analog Input Units W592...
Страница 300: ...Appendices A 62 NX series Analog I O Units User s Manual for High speed Analog Input Units W592...
Страница 301: ...I Index I 1 NX series Analog I O Units User s Manual for High speed Analog Input Units W592 I...
Страница 303: ...W Wiring Terminal 4 7 Index I 3 NX series Analog I O Units User s Manual for High speed Analog Input Units W592 I...
Страница 304: ......
Страница 305: ......