125
Wiring CP1H CPU Units
Section 3-4
3-4-3
Wiring Safety and Noise Controls
I/O Signal Wiring
Whenever possible, place I/O signal lines and power lines in separate ducts or
conduits both inside and outside of the control panel.
If the I/O wiring and power wiring must be routed in the same duct, use
shielded cables and connect the shields to the GR terminal to reduce noise.
Inductive Loads
When an inductive load is connected to an I/O Unit, connect a surge suppres-
sor or diode in parallel with the load as shown below.
Note
Use surge suppressors and diodes with the following specifications.
Noise from External
Wiring
Take the following points into account when externally wiring I/O, power sup-
ply, and power lines.
• When multi-conductor signal cable is being used, avoid combining I/O
wires and other control wires in the same cable.
• If wiring racks are parallel, allow at least 300 mm between the Racks.
(1)
(2)
(1)
(2)
(1)
(2)
Suspended duct
In-floor duct
(1) = I/O cables
(2) = Power cables
Conduits
L
IN
COM
OUT
COM
OUT
COM
L
+
Diode
DC input
Relay output
Surge suppressor
Relay output or
transistor output
Diode
Surge Suppressor Specifications
Resistance: 50
Ω
Capacitance: 0.47
µ
F
Voltage: 200
V
Diode Specifications
Breakdown voltage:
3 times load voltage min.
Mean rectification current: 1 A
Содержание Sysmac CP1H
Страница 2: ......
Страница 3: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised October 2014...
Страница 4: ...iv...
Страница 10: ...x...
Страница 18: ...xviii...
Страница 22: ...xxii...
Страница 34: ...xxxiv Conformance to EC Directives 6...
Страница 76: ...42 Function Blocks Section 1 5...
Страница 176: ...142 CP series Expansion I O Unit Wiring Section 3 6...
Страница 372: ...338 Analog I O XA CPU Units Section 5 5...
Страница 578: ...544 Trouble Shooting Section 8 7...
Страница 622: ...588 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Страница 668: ...634 Standard Models Appendix A...
Страница 669: ...635 Appendix B Dimensions Diagrams X XA and Y CPU Units 90 100 110 140 150 8 85 Four 4 5 dia holes...
Страница 744: ...710 Auxiliary Area Allocations by Address Appendix D...
Страница 771: ...737 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Страница 772: ...738 Connections to Serial Communications Option Boards Appendix F...
Страница 800: ...766 Specifications for External Power Supply Expansion Appendix H...
Страница 806: ...772 Index W Work Area 165 work bits 165 work words 165 write protection 379...
Страница 808: ...774 Revision History...
Страница 809: ......