15 Ethernet
15-38
CP2E CPU Unit Software User’s Manual(W614)
Note
Make settings using the PLC settings function in the CX-Programmer (to be included in version 9.72 and
higher).
15-5-4 PLC Setup for Socket Services
Socket Services Setting
CX-Programmer tab
Setting
Built-in Ethernet
TCP/IP keep-alive
Item
Contents
Default
TCP/IP keep-alive
Set the liveness-checking interval. When socket services using either
FINS/TCP or TCP/IP are used, the connection will be terminated if there
is no response from the remote node (either a server or client) within the
time set here. (Enabled for socket services using FINS/TCP or TCP/IP
only.)
Setting range: 0 to 65,5
3
5 minutes
This setting applies to the keep-alive setting for each connection set
with the FINS/TCP Setting button.
0
(120 minutes)
Содержание SYSMAC CP Series
Страница 1: ...USER S MANUAL Cat No W614 E1 01 SYSMAC CP Series CP2E E D CP2E S D CP2E N D CP2E CPU Unit Software ...
Страница 3: ......
Страница 32: ...1 Overview 1 4 CP2E CPU Unit Software User s Manual W614 ...
Страница 44: ...3 CPU Unit Operation 3 8 CP2E CPU Unit Software User s Manual W614 ...
Страница 116: ...6 I O Allocation 6 8 CP2E CPU Unit Software User s Manual W614 ...
Страница 144: ...7 PLC Setup 7 28 CP2E CPU Unit Software User s Manual W614 ...
Страница 170: ...10 Interrupts 10 14 CP2E CPU Unit Software User s Manual W614 ...
Страница 200: ...11 High speed Counters 11 30 CP2E CPU Unit Software User s Manual W614 ...
Страница 272: ...12 Pulse Outputs 12 72 CP2E CPU Unit Software User s Manual W614 ...
Страница 278: ...13 PWM Outputs 13 6 CP2E CPU Unit Software User s Manual W614 ...
Страница 460: ...18 Programming Device Operations 18 28 CP2E CPU Unit Software User s Manual W614 ...
Страница 576: ...Revision 2 CP2E CPU Unit Software User s Manual W614 ...
Страница 577: ......