11 High-speed Counters
11-4
CP2E CPU Unit Software User’s Manual(W614)
Built-in Input Tab Page
* Only a software reset can be used if an increment pulse input is specified.
Note
The power supply must be restarted after the PLC Setup is transferred in order to enable the high-speed
counter settings.
z
Pulse Input Method and High-speed Counter Input Terminals
The following input terminals can be used for high-speed counters with the pulse input method.
E20/30/40/60, S30/40/60 or N20/30/40/60 CPU Units
Item
Setting
Use high
speed
counter 0
to 5
Use high-speed
counter
Select
U
s
e high
s
peed counter
for each counter to be used.
Counting Mode
Select
Linear mode or Circular mode.
Circular Max. Count
(maximum ring count)
If circular mode is selected, set the maximum ring count.
0 to 4,294,967,295 decimal
Reset
•
Phase Z and software reset
•
Software reset*
•
Phase Z and software reset (continue comparing)
•
Software reset (continue comparing)*
Input Setting
•
Differential phase inputs (4×)
•
Pulse + direction inputs
•
Up/down pulse inputs
•
Increment pulse input
Determining High-speed Counter
Input terminal block
Pulse input method (Counting mode)
Other functions that cannot be used at the same time
Terminal
block
label
Terminal
Increment
pulse input
Differential phase
×
4 or up/down
input
Pulse/
direction
input
Normal input
Interrupt
input
Quick-response
input
Origin searches
for pulse out-
puts 0 to 3
CIO 0
00
High-speed
Counter 0,
increment
input
High-speed
Counter 0, phase A
or up input
High-speed
Counter 0,
pulse input
Normal input 0
−
−
−
01
High-speed
Counter 1,
increment
input
High-speed
Counter 0, phase B
or down input
High-speed
Counter 1,
pulse input
Normal input 1
−
−
−
02
High-speed
Counter 2,
increment
input
High-speed
Counter 1, phase A
or up input
High-speed
Counter 0,
direction
Normal input 2
Interrupt input 2
Quick-response
input 2
−
0
3
−
High-speed
Counter 1, phase B
or down input
High-speed
Counter 1,
direction
Normal input
3
Interrupt input
3
Quick-response
input
3
−
04
High-speed
Counter
3
,
increment
input
High-speed
Counter 0, phase Z
or reset input
High-speed
Counter 0,
reset input
Normal input 4
Interrupt input 4
Quick-response
input 4
−
05
High-speed
Counter 4,
increment
input
High-speed
Counter 1, phase Z
or reset input
High-speed
Counter 1,
reset input
Normal input 5
Interrupt input 5
Quick-response
input 5
−
06
High-speed
Counter 5,
increment
input
−
−
Normal input 6
Interrupt input 6
Quick-response
input 6
Pulse 0, Origin
input signal
07
−
−
−
Normal input 7
Interrupt input 7
Quick-response
input 7
Pulse 1, Origin
input signal
0
8
−
−
−
Normal input
8
Interrupt input
8
(Note 1)
Quick-response
input
8
(Note 1)
Pulse 2, Origin
input signal
(Note 2)
Содержание SYSMAC CP Series
Страница 1: ...USER S MANUAL Cat No W614 E1 01 SYSMAC CP Series CP2E E D CP2E S D CP2E N D CP2E CPU Unit Software ...
Страница 3: ......
Страница 32: ...1 Overview 1 4 CP2E CPU Unit Software User s Manual W614 ...
Страница 44: ...3 CPU Unit Operation 3 8 CP2E CPU Unit Software User s Manual W614 ...
Страница 116: ...6 I O Allocation 6 8 CP2E CPU Unit Software User s Manual W614 ...
Страница 144: ...7 PLC Setup 7 28 CP2E CPU Unit Software User s Manual W614 ...
Страница 170: ...10 Interrupts 10 14 CP2E CPU Unit Software User s Manual W614 ...
Страница 200: ...11 High speed Counters 11 30 CP2E CPU Unit Software User s Manual W614 ...
Страница 272: ...12 Pulse Outputs 12 72 CP2E CPU Unit Software User s Manual W614 ...
Страница 278: ...13 PWM Outputs 13 6 CP2E CPU Unit Software User s Manual W614 ...
Страница 460: ...18 Programming Device Operations 18 28 CP2E CPU Unit Software User s Manual W614 ...
Страница 576: ...Revision 2 CP2E CPU Unit Software User s Manual W614 ...
Страница 577: ......