V600/V620 ID Controller Protocol
Appendix P
Receive Data Word Allocation (4th Operand of PMCR(260))
Note
Data for Data Carriers designated for hexadecimal is sent beginning with the largest offset from the
receive data words.
Auto-read (ASCII/1) (Sequence No. 508 (Hex 01FC))
This sequence is used when the maximum number of Heads to be read from the Carrier is 1.
Send Data Word Allocation (3rd Operand of PMCR(260))
The send data word allocation is similar to that of Sequence No. 500 (Read (ASCII/1)).
Receive Data Word Allocation (4th Operand of PMCR(260))
The receive data word allocation is similar to that of Sequence No. 500 (Read (ASCII/1)).
Note
For auto-read (AR), a response is not returned if the number of Heads is not read by the Carrier, the
Abort Bit must be turned OFF to terminate the sequence.
Auto-read (Hex/1) (Sequence No. 509 (Hex 01FD))
This sequence is used when the maximum number of Heads to be read from the Carrier is 1.
Send Data Word Allocation (3rd Operand of PMCR(260))
The send data word allocation is similar to that of Sequence No. 504 (Read (Hex/1)).
Receive Data Word Allocation (4th Operand of PMCR(260))
The receive data word allocation is similar to that of Sequence No. 504 (Read (Hex/1)).
Note
For auto-read (AR), a response is not returned if the number of Heads is not read by the Carrier, the
Abort Bit must be turned OFF to terminate the sequence.
Offset
Contents (data format)
Data
+0
Number of receive data
words (4 digits Hex)
0002 to 004C (2 to 76 decimal)
+(10(N–1)+1) to
+(10(N–1)+5)
Read data (CH 1) (Hex)
Number of read bytes stored in hexadecimal
data
N: Number of Heads
Receive data
storage words
Number of receive data words
+0
+1
+5
+6
+10
+11
+15
+71
+75
~
~
Read data
Read data
CH 1
CH 2
Not used
~
~
Not used
~
~
~
~
Read data
Read data
CH 8
Read data
~
~
Read data
Содержание SYSMAC CJ1W-SCU21-V1
Страница 3: ...iv...
Страница 5: ...vi...
Страница 9: ...x...
Страница 15: ...xvi...
Страница 89: ...60 Basic Operating Procedure Section 1 9...
Страница 151: ...122 RS 232C and RS 422A 485 Wiring Section 3 4...
Страница 173: ...144 Host Link Function for Replacing Existing PLCs Section 4 6...
Страница 223: ...194 Enhanced Protocol Macro Functions Section 5 6...
Страница 277: ...248 Communications Frames Section 6 8...
Страница 291: ...262 Basic Operating Procedure in No protocol Mode Section 7 4...
Страница 301: ...272 Auxiliary Area and CIO Area Allocations Section 8 3...
Страница 391: ...362 Introduction Appendix A...
Страница 421: ...392 CompoWay F Master Protocol Appendix B...
Страница 513: ...484 E5 K Digital Controller Read Protocol Appendix F...
Страница 571: ...542 E5ZE Temperature Controller Write Protocol Appendix I...
Страница 587: ...558 E5 J Temperature Controller Protocol Appendix J...
Страница 627: ...598 ES100 Digital Controller Protocol Appendix K...
Страница 661: ...632 V500 V520 Bar Code Reader Protocol Appendix M...
Страница 697: ...668 3Z4L Laser Micrometer Protocol Appendix N...
Страница 717: ...688 Visual Inspection System Protocol Appendix O...
Страница 755: ...726 V600 V620 ID Controller Protocol Appendix P...
Страница 763: ...734 Hayes Modem AT Command Protocol Appendix Q...
Страница 767: ...738 Changing Communications Port Settings Using STUP 237 Appendix R...
Страница 781: ...752 Revision History...