324
Troubleshooting
Section 11-3
Troubleshooting Using FINS End Codes
MRC
(Main response code)
SRC
(Sub-response code)
Check point
Probable cause
Corrective measure
Value
(hex)
Contents
Value
(hex)
Contents
00
Normal comple-
tion
00
Normal comple-
tion
---
---
---
04
Remote node
busy
Bit 05 in CIO word
n+8/n+18 (Serial
Gateway timeout or
Serial Gateway
response timeout)
The Serial Gateway
cannot be executed
as an interrupt
between steps in the
protocol macro.
Perform FINS send
retry processing or
change the commu-
nications sequence.
02
Remote node
error
05
Response time-
out at FINS
transmission
source
Bit 05 in CIO word
n+8/n+18 (Serial
Gateway timeout or
Serial Gateway
response timeout)
The message frame
was destroyed by
noise.
If Bit 05 of CIO word
n+8/n+18 is OFF, a
response timeout
has occurred at the
FINS transmission
source. Perform the
following:
Test communica-
tions to check the
noise conditions.
Increase the num-
ber of retries at the
FINS command
transmission source.
Perform communica-
tions retries, if nec-
essary.
Instruction control
data
The response moni-
toring time is too
short.
Increase the length
of the response
monitoring time.
Error history
The send/receive
frame was dis-
carded.
Take appropriate
measures based on
the error history.
Serial Gateway
response time-
out
Bit 05 in CIO word
n+8/n+18 (Serial
Gateway timeout or
Serial Gateway
response timeout)
A Serial Gateway
response timeout
has occurred.
If bit 05 of CIO word
n+8/n+18 is ON,
take appropriate
measures for a
Serial Gateway
response timeout.
06
Transmission
path error
CIO word n+8/n+18
bit 07 (FCS check
error) or bit 02 (parity
error)
Conversion to Com-
poWay/F command:
BCC error or parity
error
Conversion to Mod-
bus-RTU command:
CRC error or parity
error
Conversion to Mod-
bus-ASCII com-
mand: CRC error or
checksum error
Use shielded
twisted-pair cables.
Lay power lines sep-
arately using ducts.
Increase the num-
ber of resends at the
FINS transmission
source.
Perform communica-
tions retry as
required.
10
Command for-
mat error
01
Command too
long
Command data
The command is
longer than the maxi-
mum permissible
length.
Check the command
format and correct
the command data.
02
Command too
short
Command data
The command is
shorter than the
maximum permissi-
ble length.
Check the command
format and correct
the command data.
Содержание SYSMAC CJ1W-SCU21-V1
Страница 3: ...iv...
Страница 5: ...vi...
Страница 9: ...x...
Страница 15: ...xvi...
Страница 89: ...60 Basic Operating Procedure Section 1 9...
Страница 151: ...122 RS 232C and RS 422A 485 Wiring Section 3 4...
Страница 173: ...144 Host Link Function for Replacing Existing PLCs Section 4 6...
Страница 223: ...194 Enhanced Protocol Macro Functions Section 5 6...
Страница 277: ...248 Communications Frames Section 6 8...
Страница 291: ...262 Basic Operating Procedure in No protocol Mode Section 7 4...
Страница 301: ...272 Auxiliary Area and CIO Area Allocations Section 8 3...
Страница 391: ...362 Introduction Appendix A...
Страница 421: ...392 CompoWay F Master Protocol Appendix B...
Страница 513: ...484 E5 K Digital Controller Read Protocol Appendix F...
Страница 571: ...542 E5ZE Temperature Controller Write Protocol Appendix I...
Страница 587: ...558 E5 J Temperature Controller Protocol Appendix J...
Страница 627: ...598 ES100 Digital Controller Protocol Appendix K...
Страница 661: ...632 V500 V520 Bar Code Reader Protocol Appendix M...
Страница 697: ...668 3Z4L Laser Micrometer Protocol Appendix N...
Страница 717: ...688 Visual Inspection System Protocol Appendix O...
Страница 755: ...726 V600 V620 ID Controller Protocol Appendix P...
Страница 763: ...734 Hayes Modem AT Command Protocol Appendix Q...
Страница 767: ...738 Changing Communications Port Settings Using STUP 237 Appendix R...
Страница 781: ...752 Revision History...