305
Setup Area Allocations
Section 10-2
5.
Turn ON the Loopback Test Switch. To end the test, turn OFF the switch.
The Loopback Test Switches are as follows:
Board:
CIO 1900, bit 06 for port 1 and bit 14 for port 2
Unit:
n, bit 06 for port 1 and bit 14 for port 2 (n = CIO 1500 + 25 x
Unit No.)
Refer to
6.
Use the protocol status to check the results.
Refer to
10-1-4 Indicators Used for the Loopback Test
When the test is being executed, the indicators shown below will flash. Use
the protocol status to check whether or not the test has been executed nor-
mally.
Serial Communications
Boards (CS Series Only)
Port 1: COMM1 indicator
Port 2: COMM2 indicator
Serial Communications
Units (CS/CJ Series)
Port 1: SD1/RD1 indicator
Port 2: SD2/RD2 indicator
10-2 Setup Area Allocations
This section describes the Setup Area allocated to the Serial Communications
Board and Serial Communications Units in the DM Area when loopback tests
are performed.
The loopback test is performed using the Host Link mode protocol. The Setup
is basically the same as for the Host Link mode.
m = 100
×
unit number
Serial Communications
Mode
Set the serial communications mode to F Hex to perform a loopback test.
For the other settings, refer to
4-2 Setup Area Allocations.
DM Area
Bit
Settings
Board
(CS Series only)
Unit
(CS/CJ Series)
Port 1
Port 2
Port 1
Port 2
D32000
D32010
m
m + 10
15
Port settings
0: Defaults, 1: User settings
14 to 12
Reserved
11 to 08
Serial communications mode: Always F Hex (Loopback test)
07 to 05
Reserved
04
Start bits
0: 1 bit; 1: 1 bit (1 start bit is always used regardless of this setting)
03
Data length
0: 7 bits, 1: 8 bits
02
Start bits
0: 2 bits, 1: 1 bit
01
Parity
0: Yes, 1: No
00
Parity
0: Even, 1: Odd
D32001
D32011
m + 1
m + 11
15 to 04
Reserved
03 to 00
Baud rate (bps)
0 hex: Default (9,600); 3 hex: 1,200; 4 hex: 2,400; 5 hex: 4,800;
6 hex: 9,600; 7 hex: 19,200; 8 hex: 38,400; 9 hex: 57,600;
A hex: 115,200
Содержание SYSMAC CJ1W-SCU21-V1
Страница 3: ...iv...
Страница 5: ...vi...
Страница 9: ...x...
Страница 15: ...xvi...
Страница 89: ...60 Basic Operating Procedure Section 1 9...
Страница 151: ...122 RS 232C and RS 422A 485 Wiring Section 3 4...
Страница 173: ...144 Host Link Function for Replacing Existing PLCs Section 4 6...
Страница 223: ...194 Enhanced Protocol Macro Functions Section 5 6...
Страница 277: ...248 Communications Frames Section 6 8...
Страница 291: ...262 Basic Operating Procedure in No protocol Mode Section 7 4...
Страница 301: ...272 Auxiliary Area and CIO Area Allocations Section 8 3...
Страница 391: ...362 Introduction Appendix A...
Страница 421: ...392 CompoWay F Master Protocol Appendix B...
Страница 513: ...484 E5 K Digital Controller Read Protocol Appendix F...
Страница 571: ...542 E5ZE Temperature Controller Write Protocol Appendix I...
Страница 587: ...558 E5 J Temperature Controller Protocol Appendix J...
Страница 627: ...598 ES100 Digital Controller Protocol Appendix K...
Страница 661: ...632 V500 V520 Bar Code Reader Protocol Appendix M...
Страница 697: ...668 3Z4L Laser Micrometer Protocol Appendix N...
Страница 717: ...688 Visual Inspection System Protocol Appendix O...
Страница 755: ...726 V600 V620 ID Controller Protocol Appendix P...
Страница 763: ...734 Hayes Modem AT Command Protocol Appendix Q...
Страница 767: ...738 Changing Communications Port Settings Using STUP 237 Appendix R...
Страница 781: ...752 Revision History...