241
Communications Frames
Section 6-8
Response Frame
6-8-5
Sending Commands Using the CMND(490) Instruction
Use the following method to send FINS commands to the Serial Communica-
tions Board/Unit from the PLC.
Setting CMND(490) Operands
S Operand
• Set the FINS command code (2803/2804/2805 hex) in S.
• Set the data without spaces (see note) following the FINS command code
in S+1 onwards.
Note
Frames are set in the same order as in I/O memory from leftmost to rightmost
byte (without blank bytes (00 hex)).
C Operand
C+2 bits 00 to 07 (Send destination network address)
• With routing tables that treat serial communications path as a network:
Network address corresponding to serial port in the routing tables.
• Without routing tables that treat serial communications path as a network:
• CompoWay/F, Modbus: Depends on the system configuration.
• Host Link FINS: Always set the unit address of the serial port.
C+3 bits 08 to 15 (Remote destination node address)
• CompoWay/F, Modbus
• With routing tables that treat serial communications path as a network:
00 hex (indicates local PLC communications)
• Without routing tables that treat serial communications path as a net-
work: Node address for specifying the actual remote PLC
• Host Link FINS
• Host Link unit number incremented by one (1 to 32)
C+3 bits 00 to 07 (Send destination unit address)
• CompoWay/F, Modbus
Always set the unit address of the serial port
Frame before Conversion
Host
Link
header
code
@
Unit No. for
Host Link
(0 to 31)
Etc.
FINS header
Host Link
header
FA
Text
End code
FINS text
Error
check
code
Terminator
FCS
*+CR
End code
FINS header
FINS text
User-specified
SRC
MRC
Remote
network
address
(DNA)
Remote
node
address
(DA1)
Remote
unit
address
(DA2)
Etc.
Serial port
allocated
address
or serial
port unit
address
Unit No.
for Host
Link
+ 1
(1 to 32)
Any
except
serial
port
unit
address
Frame after Conversion
FINS
command
FINS
command
User-
speci-
fied
User-
speci-
fied
Содержание SYSMAC CJ1W-SCU21-V1
Страница 3: ...iv...
Страница 5: ...vi...
Страница 9: ...x...
Страница 15: ...xvi...
Страница 89: ...60 Basic Operating Procedure Section 1 9...
Страница 151: ...122 RS 232C and RS 422A 485 Wiring Section 3 4...
Страница 173: ...144 Host Link Function for Replacing Existing PLCs Section 4 6...
Страница 223: ...194 Enhanced Protocol Macro Functions Section 5 6...
Страница 277: ...248 Communications Frames Section 6 8...
Страница 291: ...262 Basic Operating Procedure in No protocol Mode Section 7 4...
Страница 301: ...272 Auxiliary Area and CIO Area Allocations Section 8 3...
Страница 391: ...362 Introduction Appendix A...
Страница 421: ...392 CompoWay F Master Protocol Appendix B...
Страница 513: ...484 E5 K Digital Controller Read Protocol Appendix F...
Страница 571: ...542 E5ZE Temperature Controller Write Protocol Appendix I...
Страница 587: ...558 E5 J Temperature Controller Protocol Appendix J...
Страница 627: ...598 ES100 Digital Controller Protocol Appendix K...
Страница 661: ...632 V500 V520 Bar Code Reader Protocol Appendix M...
Страница 697: ...668 3Z4L Laser Micrometer Protocol Appendix N...
Страница 717: ...688 Visual Inspection System Protocol Appendix O...
Страница 755: ...726 V600 V620 ID Controller Protocol Appendix P...
Страница 763: ...734 Hayes Modem AT Command Protocol Appendix Q...
Страница 767: ...738 Changing Communications Port Settings Using STUP 237 Appendix R...
Страница 781: ...752 Revision History...