1 Introduction
1-16
CJ-series EtherNet/IP Units Operation Manual for NJ-series CPU Unit (W495)
1-4
Introduction to Communications
Services
A program is not required to perform cyclic data exchanges with other devices on the EtherNet/IP net-
work. Normally, a connection is started with the target device for each tag set that was created with the
Network Configurator to start communications for tag data links for an EtherNet/IP Unit. One connection
is used per tag set. You can register up to 256 connections. The following table gives the EtherNet/IP
Unit tag and tag set specifications.
* In this example, a connection is established with the originator’s tag list with tags a to g (inputs), which are in a
tag set called SP1_IN, and the target’s tag list with tags i and ii (outputs), which are in a tag set called SP1_OUT.
1-4-1
CIP (Common Industrial Protocol) Communications Services
Tag Data Links (Cyclic Communications)
Tags
Tag sets
Total size of all tags
≤
184,832 words
Maximum size of 1 tag set
≤
722 words
(The maximum size is 721 words when the tag set
includes the Controller status.)
Maximum size of 1 tag
≤
722 words
(The maximum size is 721 words when the tag set
includes the Controller status.)
Number of tags per tag set
≤
8
(7 tags/tag set when the tag set includes the Controller
status)
Note
Input and output variables cannot be combined.
Number of registrable tags
≤
256
Number of registrable tag sets
≤
256
EtherNet/IP
Tag ii
Originator device
Target device
Tag i
Controller Status
Tag set name: SP1_OUT
Tag Set (Output)
Data flow
Connection
Tag g
Tag c
Tag b
Tag a
Controller status
Tag set name: SP1_IN
Tag Set (Input)
• Packet interval (RPI)
• Originator tag set
• Target tag set
• Target IP address
Connection Information
Содержание SYSMAC CJ1W-EIP21
Страница 8: ...Manual Structure 6 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Страница 10: ...Sections in this Manual 8 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Страница 20: ...Read and Understand this Manual 18 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Страница 42: ...Revision History 40 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Страница 68: ...1 Introduction 1 26 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Страница 80: ...2 Installing Ethernet Networks 2 12 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Страница 130: ...6 Testing Communications 6 4 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Страница 206: ...7 Tag Data Link Functions 7 76 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Страница 246: ...8 Message Communications 8 40 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Страница 266: ...9 FTP Server 9 20 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Страница 374: ...13 Troubleshooting 13 56 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Страница 431: ...Index 1 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495 I Index...
Страница 436: ...Index 6 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495 Index...
Страница 437: ......