Section 4
System Connections
35
+
COM
NPN current output
IN
DC input
0 V
Output
7 mA
Current
regulator
+
COM
NPN open-collector output
Sensor
Power
Supply
IN
DC input
0 V
Output
7 mA
+
COM
PNP current output
Sensor
Power
Supply
IN
AC/DC input
0 V
Output
7 mA
AC Input
COM
Contact output
IN
AC input
COM
AC Switching
IN
AC input
Prox.
switch
main
circuit
Note
If a reed switch is used as the input contact of the AC Input Unit, the
reed switch must have a permissible current capacity of 1 A mini-
mum, otherwise contact weld may result due to inrush current.
Output Units
A fuse placed in the output circuit will protect the output element, circuit board,
etc., in the event of a short circuit in the output circuit.
COM
OUT
Relay,
solenoid, etc.
+