27
Alarm SV 1 (Display Level 0)
PV
SV
Alarm 1 parameter symbol
Alarm SV of currently selected bank and loop (unit: EU)
Invalid if ALARM mode = 0.
Alarm SV 2 (Display Level 0)
PV
SV
Alarm 2 parameter symbol
Alarm SV of currently selected bank and loop (unit: EU)
Invalid if ALARM mode = 0.
Input Shift Value (Display Level 0)
PV
SV
Input shift value parameter symbol
Input shift value of currently selected bank and loop (unit:
EU)
If the displayed value differs from the actual value due to the sensor position or
some other conditions, set the input shift value such that the correct value is dis-
played.
Proportional Band (Display Level 0)
PV
SV
Proportional Band parameter symbol
Proportional band of currently selected bank and loop
(unit: %FS)
•
This sets the proportional band. It is valid only when SW203-1 is set to OFF
(i.e., PID control).
•
This value is reflected even when auto-tuning (AT) is executed.
•
If this value is set to “0.0,” ON/OFF control is executed with PID control se-
lected.
Integral (Reset) Time (Display Level 0)
PV
SV
Integral time parameter symbol
Integral time of currently selected bank and loop
(unit: second)
•
This sets the integral time. It is valid only when SW203-1 is set to OFF (i.e., PID
control).
•
This value is reflected even when auto-tuning (AT) is executed.
Derivative (Rate) Time (Display Level 0)
PV
SV
Derivative time parameter symbol
Derivative time of currently selected bank and loop
(unit: second)
Parameter Displays and Settings