Fuses, cable cross-sections and glands
Section 14-6
14-6 Fuses, cable cross-sections and glands
14-6-1 According IEC ratings
Use mains fuses of the type gL/gG conforming to IEC 269 or installation cut-
outs with similar characteristics. Check the equipment first before installing
the glands.
Max. Fuse = maximum fuse value that still protects the VSD and upholds war-
ranty.
Note
The dimensions of fuse and cable cross-section are dependent on the
application and must be determined in accordance with local regulations.
Note
The dimensions of the power terminals used in the models 4160 to 4800 at
400 V and 6315 to 61K0 at 690 V can differ depending on customer
specification.
Table 47 Storage
Parameter
Storage condition
Temperature
-20 to +60 °C
Atmospheric pressure
86–106 kPa
Relative humidity, non-condensing 0– 90%
Table 48 Fuses, cable cross-sections and glands for 400 V
Model
Nominal
input
current [A]
Maximum
value
fuse [A]
Cable cross section connector range
[mm
2
] for
Cable glands (clamping
range [mm])
mains/motor
Brake
PE
mains/motor
Brake
SX-D40P7-EF
2.2
4
0.5 - 10
0.5 - 10
1.5 - 16
M32 opening
M20+reducer
(6 - 12)
M25 opening
M20+reducer
(6-12)
SX-D41P5-EF
3.5
4
SX-D42P2-EF
5.2
6
SX-D43P0-EF
6.9
10
M32 (12-20)
opening
M25+reducer
(10-14)
M25 (10-14)
SX-D44P0-EF
8.7
10
SX-D45P5-EF
11.3
16
M32 (16-25)/
M32 (13-18)
SX-D47P5-EF
15.6
20
SX-D4011-EF
22
25
2.5 - 16 Stranded wire
2.5 - 25 Solid wire
6 - 35
M32 (15-21)
M25
SX-D4015-EF
26
35
SX-D4018-EF
31
35
M40 (19-28)
M32
SX-D4022-EF
38
50
SX-D4030-EF
52
63
10 - 35 Stranded wire
10 - 50 Solid wire
M50 (27-35)
M40 (19-28)
SX-D4037-EF
65
80
SX-D4045-EF
78
100
16-95
16-95
16-95
(16-70)¹
Ø17-42
cable entry or
M50 (27-35)
Ø11-32
cable entry or
M40 (19-28)
SX-D4055-EF
94
100
SX-D4075-EF
126
160
35 - 150
16 - 95
35-150
(16-70)¹
SX-D4090-EF
152
160
SX-D4110-EF
182
200
35 - 250
35 - 150
35 - 250
(95-185)¹
Ø23-55
cable entry or
M63
Ø17-42
cable entry or
M50
SX-D4132-EF
216
250
SX-
@
4160-EF
260
300
(2x)35-240
frame
---
--
SX-
@
4200-EF
324
355
SX-
@
4220-EF
372
400
(2x)35-240
frame
--
--
SX-
@
4250-EF
432
500
Содержание SX-F
Страница 2: ......
Страница 14: ...6 Table of contents...
Страница 20: ...12 Glossary Section 1 6...
Страница 32: ...24 Cabinet mounting Section 2 3...
Страница 58: ...50 Connecting options Section 5 6...
Страница 72: ...64 Load Monitor and Process Protection 400 Section 7 5...
Страница 74: ...66 EMC standards Section 8 1...
Страница 266: ...258 System Data 900 Section 11 9...
Страница 274: ...266 Maintenance Section 12 3...
Страница 284: ...276 Liquid cooling Section 13 12...