Stand-alone units
Section 2-2
2-2
Stand-alone units
The VSD must be mounted in a vertical position against a flat surface. Use the
template (delivered together with the VSD) to mark out the position of the fix-
ing holes.
Fig. 6 Mounting models 4090-4800 and 6090-61K0
2-2-1
Cooling
Fig. 6 shows the minimum free space required around the VSD for the models
40P7-4800 and 6090-61K0 in order to guarantee adequate cooling. Because
the fans blow the air from the bottom to the top it is advisable not to position
an air inlet immediately above an air outlet.
The following minimum separation between two variable speed drives, or a
VSD and a non-dissipating wall must be maintained. Valid if free space on
opposite side.
Note
When a 4160-4800 or 6315-61K0 model is placed between two walls, a
minimum distance at each side of 200 mm must be maintained.
Table 4
Mounting and cooling
40P7-47P5
4011-4037
4045-4132
6090-6250
4160-4800
6315-61K0
cabinet
SX-F, side-by-side
(mm)
a
200
200
200
100
b
200
200
200
0
c
0
0
0
0
d
0
0
0
0
SX-F wall,
wall-one side
(mm)
a
100
100
100
100
b
100
100
100
0
c
0
0
0
0
d
0
0
0
0
Содержание SX-F
Страница 2: ......
Страница 14: ...6 Table of contents...
Страница 20: ...12 Glossary Section 1 6...
Страница 32: ...24 Cabinet mounting Section 2 3...
Страница 58: ...50 Connecting options Section 5 6...
Страница 72: ...64 Load Monitor and Process Protection 400 Section 7 5...
Страница 74: ...66 EMC standards Section 8 1...
Страница 266: ...258 System Data 900 Section 11 9...
Страница 274: ...266 Maintenance Section 12 3...
Страница 284: ...276 Liquid cooling Section 13 12...