180
Load Monitor and Process Protection [400]
Section 11-4
Max Alarm delay [4162]
When the load level without interruption exceeds the alarm level longer than
set “Max Alarm delay” time, an alarm is activate.
Communication information
Max Pre Alarm [417]
Max Pre AlarmMargin [4171]
With load type Basic, [415], used the Max Pre-Alarm Margin sets the band
above the Normal Load, [41B], menu that does not generate a pre-alarm.
With load type Load Curve, [415], used the Max Pre-Alarm Margin sets the
band above the Load Curve, [41C], that does not generate a pre-alarm. The
Max Pre-Alarm Margin is a percentage of nominal motor torque.
Communication information
Max Pre Alarm delay [4172]
When the load level without interruption exceeds the alarm level longer than
set “Max PreAlarm delay” time, a warning is activated.
Communication information
Default:
0.1 s
Range:
0-90 s
Modbus Instance no/
DeviceNet no:
43330
Profibus slot/index
169/234
EtherCAT index (hex)
4d02
Fieldbus format
Long, 1=0.1 s
Modbus format
EInt
Default:
10%
Range:
0–400%
Modbus Instance no/
DeviceNet no:
43327
Profibus slot/index
169/231
EtherCAT index (hex)
4cff
Fieldbus format
Long, 1=0.1%
Modbus format
EInt
Default:
0.1 s
Range:
0–90 s
Modbus Instance no/
DeviceNet no:
43331
Profibus slot/index
169/235
EtherCAT index (hex)
4d03
0.1s
A
10%
A
0.1s
A
Содержание SX-F
Страница 2: ......
Страница 14: ...6 Table of contents...
Страница 20: ...12 Glossary Section 1 6...
Страница 32: ...24 Cabinet mounting Section 2 3...
Страница 58: ...50 Connecting options Section 5 6...
Страница 72: ...64 Load Monitor and Process Protection 400 Section 7 5...
Страница 74: ...66 EMC standards Section 8 1...
Страница 266: ...258 System Data 900 Section 11 9...
Страница 274: ...266 Maintenance Section 12 3...
Страница 284: ...276 Liquid cooling Section 13 12...