166
Process and Application Parameters [300]
Section 11-3
If the speed of the pump reaches the upper band limit, the next pump is
started immediately without delay. If a start delay is used this delay will be
ignored. Range is between 0%, equalling max speed, and the set percentage
for the UpperBand [397].
Communication information
Fig. 87
Upper band limit
Lower Band Limit [39C]
If the speed of the pump reaches the lower band limit, the 'top' pump is
stopped immediately without delay. If a stop delay is used this delay will be
ignored. Range is from 0%, equalling min speed, to the set percentage for the
Lower Band [398].
Communication information
Default:
0%
Range:
0 to Upper Band level. 0% (=max speed) means that the
Limit function is switched off.
Modbus Instance no/
DeviceNet no:
43171
Profibus slot/index
169/75
EtherCAT index (hex)
4c63
Fieldbus format
Long, 1=1%
Modbus format
EInt
Default:
0%
Range:
0 to Lower Band level. 0% (=min speed) means that he
Limit function is switched off.
Modbus Instance no/
DeviceNet no:
43172
Profibus slot/index
169/76
EtherCAT index (hex)
4c64
Fieldbus format
Long, 1=1%
Modbus format
EInt
0%
A
(NG_50-PC-14_2)
Speed
Max
Min
Upper band
Start Delay [399]
Upper band
limit [39B]
next pump starts
immediately
Flow/Pressure
A
0%
Содержание SX-F
Страница 2: ......
Страница 14: ...6 Table of contents...
Страница 20: ...12 Glossary Section 1 6...
Страница 32: ...24 Cabinet mounting Section 2 3...
Страница 58: ...50 Connecting options Section 5 6...
Страница 72: ...64 Load Monitor and Process Protection 400 Section 7 5...
Страница 74: ...66 EMC standards Section 8 1...
Страница 266: ...258 System Data 900 Section 11 9...
Страница 274: ...266 Maintenance Section 12 3...
Страница 284: ...276 Liquid cooling Section 13 12...