Process and Application Parameters [300]
Section 11-3
Note
A too high level of IxR Compensation could cause motor saturation. This can
cause a “Power Fault” trip. The effect of IxR Compensation is stronger with
higher power motors.
Note
The motor may be overheated at low speed. Therefore it is important that the
Motor I
2
t Current [232] is set correctly.
Flux Optimization reduces the energy consumption and the motor noise, at
low or no load conditions.
Flux Optimization automatically decreases the V/Hz ratio, depending on the
actual load of the motor when the process is in a steady situation. Fig. 79
shows the area within which the Flux Optimization is active.
Communication information
Fig. 79
Flux Optimizing
Note
Flux optimization works best at stable situations in slow changing processes.
Maximum power [355]
Sets maximum power. Could be used for limiting motor power in field weaken-
ing operation. This function operates as an upper limit and internally limits the
parameter Max Torque [351] according to:
Tlimit = Plimit[%] / (Actual speed / Sync Speed)
Default:
Off
Off
0
Function disabled
On
1
Function enabled
Modbus Instance no/
DeviceNet no:
43144
Profibus slot/index
169/48
EtherCAT index (hex)
4c48
Fieldbus format
UInt
Modbus format
UInt
Off
A
50
Hz
f
%
U
100
Flux optimizing
area
Содержание SX-F
Страница 2: ......
Страница 14: ...6 Table of contents...
Страница 20: ...12 Glossary Section 1 6...
Страница 32: ...24 Cabinet mounting Section 2 3...
Страница 58: ...50 Connecting options Section 5 6...
Страница 72: ...64 Load Monitor and Process Protection 400 Section 7 5...
Страница 74: ...66 EMC standards Section 8 1...
Страница 266: ...258 System Data 900 Section 11 9...
Страница 274: ...266 Maintenance Section 12 3...
Страница 284: ...276 Liquid cooling Section 13 12...