131
Process and Application Parameters [300]
Section 11-3
11-3-3 Start/Stop settings [330]
Submenu with all the functions for acceleration, deceleration, starting, stop-
ping, etc.
Acceleration Time [331]
The acceleration time is defined as the time it takes for the motor to acceler-
ate from 0 rpm to nominal motor speed.
Note
If the Acc Time is too short, the motor is accelerated according to the Torque
Limit. The actual Acceleration Time may then be longer than the value set.
Communication information
Fig. 68 shows the relationship between nominal motor speed/max speed and
the acceleration time. The same is valid for the deceleration time.
Fig. 68
Acceleration time and maximum speed
Fig. 69 shows the settings of the acceleration and deceleration times with
respect to the nominal motor speed.
Default:
10.0 s
Range:
0–3600 s
331 Acc Time
Stp
10.0s
A
Modbus Instance no/
DeviceNet no:
43101
Profibus slot/index
169/5
EtherCAT index (hex)
4c1d
Fieldbus format
Long, 1=0.01 s
Modbus format
EInt
Nominal
Speed
Max
Speed
rpm
t
10s
8s
(06-F12)
100% n
MOT
80% n
MOT
Содержание SX-F
Страница 2: ......
Страница 14: ...6 Table of contents...
Страница 20: ...12 Glossary Section 1 6...
Страница 32: ...24 Cabinet mounting Section 2 3...
Страница 58: ...50 Connecting options Section 5 6...
Страница 72: ...64 Load Monitor and Process Protection 400 Section 7 5...
Страница 74: ...66 EMC standards Section 8 1...
Страница 266: ...258 System Data 900 Section 11 9...
Страница 274: ...266 Maintenance Section 12 3...
Страница 284: ...276 Liquid cooling Section 13 12...