33
F3SJ-A
User’s Manual
Chapter
2
Ba
si
c Sys
te
m
System Configuration and Functions
E
Ton: Response time of safety output's OFF to ON, Toff: Response time of safety output's ON to OFF
See p.17 for response time
Setting Change by the Setting Tool
Output operation mode and other attributes can be changed for the auxiliary output by the setting tool.
Auxiliary Output (Non-Safety Output) p.95
Resetting Lockout
When the cause of the lockout is removed, the lockout condition can be released by using either of the
following methods.
•Cycle the power back ON
•Reset input
For manual reset, apply 9 to 24V to the reset input line for 100ms or longer, and then open the switch
to apply a 0 to 1.5V signal or open circuit (pin 4/yellow).
For auto reset, set the reset line open or to 0 to 1.5V for 100ms or longer, and then apply 9 to 24V
again (pin 4/yellow).
Lockout due to an interlock wiring error and an ABC blinking error may not be released by a reset input.
ON
OFF
ON
OFF
Toff
/Blocked
Unblocked
Blocked
Unblocked
Auxiliary output 1
Safety output
Toff
x2 or less *1
Ton
Toff x2 or less *1
*1 When a reversed signal of safety output is assigned to the auxiliary output 2 by the setting tool,
a delay time of the auxiliary output 2 from the safety output is Toff x 3 or less.