Ref.: Minimum Wiring Required to Check the Operation of the F3SJ
(Wiring for auto reset mode and deactivated external device monitoring function)
Interlock Function
The F3SJ turns the safety outputs OFF when its power is turned on or its beam is interrupted and holds
this state until reset input is applied. This state is called "interlock".
Two methods can be used to reset the interlock state: "auto reset that automatically turns control
outputs ON when the interrupting object is removed" and "manual reset mode that keeps control
outputs OFF until a reset signal is provided, if the interrupting object is removed".
Auto Reset
When the interrupting object is removed from the detection zone, the safety outputs automatically turn
ON. Auto reset is used on machines where a worker is not able to enter the zone between the
detection zone and the hazardous part of the machine.
To wire auto reset:
1.
Open the interlock selection input line, or short-circuit it to 0 to 1.5V (pin 1/white).
2.
Short-circuit the reset input line to 9 to 24V (pin 4/yellow).
3.
Turn ON the power to the F3SJ.
Wiring for Auto Reset Mode p.28
Open
Open
Open
Open
Open
+24V DC
0V
Interlock selection input (White)
Emitter
Receiver
(Grey) Communication line (+)
(Pink)
Communication line (-)
0V(Blue)
0V(Blue)
Power
supply
Shield
Shield
Test input(Green)
Reset input(Yellow)
24V(Brown)
24V(Brown)
External device monitoring input (Red)
Auxiliary output 1(Yellow)
Safety output 1(Green)
Safety output 2(White)
Auxiliary output 2(Red)
S3
0V
S3 : Lockout reset switch
ޓޓ
(Short-circuit to 24V when the switch is not required.)
+24V DC
Power
supply
Interlock selection input (White)
Reset input(Yellow)