Maintenance Information Window
Section 6-3
6-3
Maintenance Information Window
This section describes the Maintenance Information Window, which can be
used to monitor the status of a Temperature Input Unit.
6-3-1
Checking Maintenance Information
There are two ways to check maintenance information. One way is to
right-click in the Main Window of the Setting Tool and select
Maintenance
Information
. The other way is to double-click the Unit in the Maintenance
Mode Window, click the
I/O Module
Tab, select the desired Unit, and click the
View
Button to display the Maintenance Information Window of the I/O Unit.
8
Off-wire Detection Flag
Turns ON when a sensor is discon-
nected or a cold junction compensator
error occurs.
OFF: Normal or the input error detec-
tion disabled setting is set to disable
detecting input errors.
ON: Disconnection or cold junction
compensator error
9
Cold junction compensator
error (GRT1-TS2T only)
OFF: Normal; ON: Error
10
Reserved.
---
11
Reserved.
---
12
Reserved.
---
13
Reserved.
---
14
Reserved.
---
15
Reserved.
---
Bit
Contents
Description
Содержание SMARTSLICE GRT1-DRT
Страница 1: ...OPERATION MANUAL Cat No W455 E1 08 SmartSlice GRT1 Series Slice I O Units ...
Страница 3: ...SmartSlice GRT1 Series Slice I O Units Operation Manual Revised December 2018 ...
Страница 4: ...iv ...
Страница 6: ...vi ...
Страница 20: ...xx EC Directives 6 ...
Страница 62: ...42 Connecting Turnback Cables Section 3 3 ...
Страница 250: ...230 Maintenance Information Window Section 7 3 Maintenance Information Window ...
Страница 292: ...272 GRT1 CP1 L Positioning Unit Section 7 5 ...
Страница 300: ...280 GRT1 END End Unit Section 8 5 Dimensions 11 9 11 9 55 7 1 5 19 5 83 5 2 9 2 9 OMRON ...
Страница 322: ...302 Troubleshooting by Unit Section 9 5 ...
Страница 350: ...330 Explicit Messages Appendix A ...
Страница 354: ...334 Power Consumption and Weight Tables Appendix C ...
Страница 356: ...336 I O Current Consumption Table Appendix D ...
Страница 364: ...344 Revision History ...
Страница 365: ......