Overview of the Temperature Input Units
Section 6-1
6-1
Overview of the Temperature Input Units
This section provides an overview of the Temperature Input Units, including
details on functions and setting methods.
6-1-1
Temperature Input Units
In addition to the functions common to the GRT1 Series (backup, restore,
online conversion, etc.), other functions specific to the Temperature Input
Units (scaling, peak/bottom hold, etc.) are available. The Temperature Input
Units are also able to internally perform math on temperature input values,
which previously required ladder programming in the host PLC. Temperature
data can be selected from the six values obtained from math operations and
allocated as I/O in combination with Status Flags or other status information.
The Setting Tool can be used to allocate this status data, to make settings for
monitoring and specific Temperature Input Unit functions, and to monitor
operation.
6-1-2
Comparison with Previous Models with Platinum Resistance
Thermometer Inputs
Series
GRT1 Series
DRT2 Series
Model
GRT1-TS2P
GRT1-TS2PK
DRT2-TS04P
Input type
Platinum resistance thermometer input
Maintenance method
Terminal block and main block can be
separated.
Removable terminal block
Input type setting method
Hardware DIP switch setting, software Setting Tool. Each input bit can be set up
individually when using the Setting Tool.
Input type (sensor type)
PT100 (
−
200 to
850
°
C) or
PT100
(−
200 to
200
°
C)
PT1000 (
−
200 to
850
°
C) or
PT1000
(−
200 to
200
°
C)
PT, JPT, PT2, or JPT2
Input accuracy
−
200 to 850
°
C input range: (
±
0.3% of indication value or
±
0.8°C, whichever is
larger)
±
1 digit max.
−
200 to 200°C input range: (
±
0.3% of indication value or
±
0.5°C, whichever is
larger)
±
1 digit max.
Conversion cycle
250 ms/2 points
250 ms/4 points
1/100 display mode
The temperature data is multiplied by 100 and sent to the Master as 8-digit
binary data. (The data for each input consists of two words.)
DRT1-compatible 1/100 display mode Not
supported.
Supported.
Unit power supply
Supplied from slice bus.
Supplied from communications
power supply.
Communications power supply current
consumption
None
70 mA max.
Connections
None
Poll, Bitstrobe, and COS/cyclic
Allocated I/O data
Default: Temperature data for 2 points
The Setting Tool can be used to allocate
the peak value, bottom value, top value,
valley value, rate of change, comparator
results, Status Flags, etc.
Default: Temperature data for 4
points
The DeviceNet Configurator can be
used to allocate peak value, bottom
value, top value, valley value, rate of
change, comparator results, Status
Flags, etc.
Node address setting
No setting required.
Set using the rotary switches or the
DeviceNet Configurator.
Baud rate setting
No setting required.
Automatically detected: Uses baud
rate set for Master Unit.
Содержание SMARTSLICE GRT1-DRT
Страница 1: ...OPERATION MANUAL Cat No W455 E1 08 SmartSlice GRT1 Series Slice I O Units ...
Страница 3: ...SmartSlice GRT1 Series Slice I O Units Operation Manual Revised December 2018 ...
Страница 4: ...iv ...
Страница 6: ...vi ...
Страница 20: ...xx EC Directives 6 ...
Страница 62: ...42 Connecting Turnback Cables Section 3 3 ...
Страница 250: ...230 Maintenance Information Window Section 7 3 Maintenance Information Window ...
Страница 292: ...272 GRT1 CP1 L Positioning Unit Section 7 5 ...
Страница 300: ...280 GRT1 END End Unit Section 8 5 Dimensions 11 9 11 9 55 7 1 5 19 5 83 5 2 9 2 9 OMRON ...
Страница 322: ...302 Troubleshooting by Unit Section 9 5 ...
Страница 350: ...330 Explicit Messages Appendix A ...
Страница 354: ...334 Power Consumption and Weight Tables Appendix C ...
Страница 356: ...336 I O Current Consumption Table Appendix D ...
Страница 364: ...344 Revision History ...
Страница 365: ......