B - 9
Appendices B STO Function
High-function General-purpose Inverter RX2 Series User’s Manual
B
-2 Proce
dure f
o
r Use
of ST
O
Fu
n
ct
ion
B
B-2-
5 Status Indication F
unction
STO input status can be displayed on LCD operator when you set parameters shown below table.
You can also check the status by checking the monitor parameter [dA-45].
B-2-5
Status Indication Function
Parameters Related to STO Function Indication
Item
Parameter
Data
Description
STO input indication
selection
[bd-01]
00
If input of both ST1 and ST2 is STO (input contact point
is OFF), “STO” is shown on the control panel screen.
01
Also if input of both ST1 and ST2 is STO (input contact
point is OFF), “STO” is not shown on the control panel.
02
If input of both ST1 and ST2 is STO (input contact point
is OFF), [E090] error occurs.
*1
*1. Even if either ST1 and ST2 is set to STO, [E090] error does not occur.
STO allowable input
switch time
[bd-02]
0.00 to 60.00 (s) Set the allowable time during which input status of ST1
and ST2 is different (e.g., input contact point: ST1=ON,
ST2=OFF).
If there is a difference between the switching time of
ST1 and that of ST2, set the maximum allowable time
the difference can be generated.
If it is set to 0.00, the determination of allowable time
becomes invalid.
STO indication
selection within allow-
able input time
[bd-03]
00
Displays a warning at the time difference of status
occurs between ST1 and ST2 until the STO allowable
input switch time configured in [bd-02] has elapsed.
01
Does not display a warning at the time difference of
status occurs between ST1 and ST2 until the STO
allowable input switch time configured in [bd-02] has
elapsed.
STO operation
selection after allow-
able input time
[bd-04]
00
Displays a warning after the STO allowable input
switch time configured in [bd-02] has elapsed.
01
Does not display a warning after the STO allowable
input switch time configured in [bd-02] has elapsed.
02
After the STO allowable input switch time configured in
[bd-02] has elapsed, [E092] or [E093] error occurs.
Содержание RX - 2
Страница 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Страница 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Страница 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Страница 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Страница 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Страница 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Страница 919: ......