11 - 29
11 Options
High-function General-purpose Inverter RX2 Series User’s Manual
11-5
DC Reac
tor (
M
ode
l:
3G3AX-D
L
)
11
11-5-
3 Connection Examp
les
• These terminals are used to connect the optional DC reactor for power factor improvement.
By factory setting, a short-circuit bar is connected between the terminals PD and P. Before connect-
ing the DC reactor, remove this short-circuit bar.
• The length of the DC reactor connection cable must be 5 m or shorter.
• The DC reactor has no polarity.
Precautions for Correct Use
Precautions for Correct Use
Remove the short-circuit bar only if you connect the DC reactor for use.
If you remove the short-circuit bar with the DC reactor unconnected, the inverter cannot oper-
ate because no power is supplied to its main circuit.
11-5-3 Connection Examples
DC Reactor Connection Terminals (PD, P)
P
M
PD
DC reactor
(option)
R/L1
S/L2
T/L3
U/T1
V/T2
W/T3
3-phase 200 VAC
3-phase 400 VAC
Power
supply
MC
MCCB
Содержание RX - 2
Страница 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Страница 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Страница 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Страница 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Страница 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Страница 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Страница 919: ......