9 Communications Functions
High-function General-purpose Inverter RX2 Series User’s Manual
9-
5 Mod
bu
s Com
m
u
n
icat
ion
Regi
ster Nu
m
b
er
List
9
9-5-
2 Group d
Register
List
Precautions for Correct Use
Precautions for Correct Use
• The “Register No.” in the table header shows the register number used inside the inverter.
• The “Modbus register spec. No.” in the table header shows the register number used to actu-
ally specify the register in the Modbus communication process.
This register number is 1 less than the inverter “Register No.” according to the Modbus com-
munication specifications.
9-5-2
Group d Register List
Register
No.
Modbus
register
spec. No.
Function name
Parameter
No.
R/W
Monitor or setting data
Resolution
2711h
2710h
Output frequency monitor
dA-01
R
0 to 59000
0.01(Hz)
2712h
2711h
Output current monitor
dA-02
R
0 to 65535
0.01(A)
2713h
2712h
Operation direction monitor
dA-03
R
00: o (Stopped)
01: d (0Hz output)
02: F (Normal rotation in process)
03: r (Reverse rotation in pro-
cess)
-
2714h
2713h
Frequency command after
calculation
dA-04
(HIGH)
R
-59000 to 59000
0.01(Hz)
2715h
2714h
dA-05
(LOW)
R
2716h
2715h
Output frequency conver-
sion monitor
dA-06
(HIGH)
R
0 to 5900000
0.01
2717h
2716h
dA-07
(LOW)
R
2718h
2717h
Speed detection value moni-
tor
dA-08
(HIGH)
R
-59000 to 59000
0.01(Hz)
2719h
2718h
dA-09
(LOW)
R
271Ch
2719h
Output frequency monitor
(with sign)
dA-12
(HIGH)
R
-59000 to 59000
0.01(Hz)
271Dh
271Ch
dA-13
(LOW)
R
271Eh
271Dh
Frequency upper limit moni-
tor
dA-14
R
0 to 59000
0.01(Hz)
271Fh
271Eh
Torque command monitor
after calculation
dA-15
R
-10000 to 10000
0.1(%)
2720h
271Fh
Torque limit monitor
dA-16
R
0 to 5000
0.1(%)
2721h
2720h
Output torque monitor
dA-17
R
-10000 to 10000
0.1(%)
2722h
2721h
Output voltage monitor
dA-18
R
0 to 8000
0.1(V)
2724h
2723h
Current position monitor
dA-20
(HIGH)
R
In the case of AA121=10 and
AA123=03, data range
-2147483648 to 2147483647.
In the case of the condition men-
tioned above, data range
-536870912 to 536870911
1(pls)
2725h
2724h
dA-21
(LOW)
R
272Ah
2729h
Pulse train position deviation
monitor
dA-26
(HIGH)
R
-2147483647 to 2147483647
1(pls)
272Bh
272Ah
dA-27
(LOW)
R
Содержание RX - 2
Страница 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Страница 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Страница 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Страница 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Страница 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Страница 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Страница 919: ......