8 - 175
8 Applied Settings
High-function General-purpose Inverter RX2 Series User’s Manual
8-1
1 Ou
tpu
t T
ermin
al Fu
n
ction
8
8-1
1-2 Output
Terminal NO/
NC Selections
You can set output specifications for Contact a or Contact b separately for Output terminals 11 to 15
and Relay output terminals 16 and 17.
Parameter
• Contact a: Closes with “ON,” and opens with “OFF.”
• Contact b: Closes with “OFF,” and opens with “ON.”
062
LOG1
Result of logical operation 1
063
LOG2
Result of logical operation 2
064
LOG3
Result of logical operation 3
065
LOG4
Result of logical operation 4
066
LOG5
Result of logical operation 5
067
LOG6
Result of logical operation 6
068
LOG7
Result of logical operation 7
069
MO1
General purpose output 1
070
MO2
General purpose output 2
071
MO3
General purpose output 3
072
MO4
General purpose output 4
073
MO5
General purpose output 5
074
MO6
General purpose output 6
075
MO7
General purpose output 7
076
EMFC
During-Em-Force signal
077
EMBP
During-bypass-mode signal
080
LBK
Flat battery of LCD operator
081
OVS
Excessive voltage of accepted power
084
AC0
Alarm code bit 0
085
AC1
Alarm code bit 1
086
AC2
Alarm code bit 2
087
AC3
Alarm code bit 3
089
OD3
PID3 excessive deviation
090
FBV3
PID3 feedback comparison
091
OD4
PID4 excessive deviation
092
FBV4
PID4 feedback comparison
093
SSE
PID soft start abnormality
8-11-2 Output Terminal NO/NC Selections
Item
Parameter
Data
Description
Output terminal func-
tion selection
[CC-11] to
[CC-15]
00, 01
00: Contact a (normally open) operation
01: Contact b (normally closed) operation
Relay output terminal
function selection a/b
(NO/NC) selection
[CC-16]
Relay output terminal
function selection a/b
(NO/NC) selection
[CC-17]
Function No.
Abbreviation
Function name
Page
Содержание RX - 2
Страница 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Страница 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Страница 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Страница 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Страница 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Страница 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Страница 919: ......