8 Applied Settings
8 - 78
High-function General-purpose Inverter RX2 Series User’s Manual
The speed deviation error detection judges an error when the deviation between the output frequency
and the feedback speed becomes large.
This function operates when other than “0.0” is specified for [bb-83] Speed deviation error detection
level setting.
The speed deviation is the difference between [dA-12] output frequency monitor and [dA-08] speed
detection monitor.
When the absolute value of speed deviation has exceeded [bb-83] Speed deviation error detection level
and [bb-84] Speed deviation error detection time has elapsed, it is judged as a speed deviation error.
If “00: Warning” is specified for [bb-82] Operation for speed deviation error, the inverter turns on the
Output terminal function 041 [DSE] with a speed deviation error.
If “01: Error” is specified for [bb-82] Operation for speed deviation error, the inverter turns on the Output
terminal function 041 [DSE] with a speed deviation error, and trips with [E105] Speed deviation exces-
sive error.
Precautions for Correct Use
To use this function, speed feedback by the encoder is required.
Parameter
8-3-8
Speed Deviation Error Detection
Item
Parameter
Data
Description
Default
data
Speed deviation error
mode selection
[bb-82]
00
Turns on the output terminal function 041
[DSE].
00
01
Turns on the output terminal function 041
[DSE], and trips with [E105] Speed deviation
excessive error.
Speed deviation error
detection level
[bb-83]
0.0 to 100.0(%)
Set the level at 100% to which the maximum
frequency is set.
15.0
Speed deviation error
detection time
[bb-84]
0.0 to 5.0(s)
Sets the time to judge the deviation to be an
error after it has excessively increased.
0.5
Speed Detection
Values monitor
[dA-08]
-590.00 to
590.00(Hz)
Displays data obtained through encoder
feedback.
-
Output frequency
monitor
[dA-12]
-590.00 to
590.00(Hz)
Displays the frequency command given by
the inverter.
-
bb -83
0
bb -83
bb -84
bb -84
bb -84
Speed
deviation
Output signal
[DSE]
Содержание RX - 2
Страница 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Страница 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Страница 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Страница 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Страница 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Страница 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Страница 919: ......