6 - 21
6 Basic Parameter Settings
High-function General-purpose Inverter RX2 Series User’s Manual
6-
3 O
peratio
n
C
omm
and
Sett
ing
s
6
6-
3-4 Opera
tion w
ith 3
Wire
F
unction
of
Ter
m
inal Block
Parameter
For 3-wire terminal commands, there are start, stop and forward/reverse operations. They are used to
start and stop the inverter via an automatic reset contact such as a pushbutton switch.
Operation start command can be given from [STA] terminal and stop command from [STP] terminal.
To use the 3 wire function, the setting of the Run-command input source selection, 1st-motor [AA111]
and the input terminal setting selection [CA-01]-[CA-11] needs to be changed.
Select [AA111]=01 3 wire function. In this example, the 3 wire function is assigned to the input terminal
function in the following way.
*1. Set the terminals as the terminal No. 7 [CA-07]=016, No. 8 [CA-08]=017, No. 9 [CA-09]=018.
Operation can be started/stopped by making the 016 [STA]/017 [STP] terminal function ON/OFF on the
control circuit terminal block of the inverter.
018 [F/R] terminal function switches forward and reverse rotations by the contact.
The terminal action is made in the following way.
Item
Parameters
Data
Description
Default
data
Run-command input
source selection,
1st-motor
[AA111]
00
Run/Stop from the control circuit terminal block.
([FW], [RV] terminals)
00
*1
*1. Default data when default data selection (UB-02) is set to 01.
Input terminal function
selection
[CA-01] to
[CA-11]
01
[FW] terminal function
-
02
[RV] terminal function
Input terminal
a/b (NO/NC) selection
[CA-21] to
[CA-31]
00
a contact (NO)
-
01
b contact (NC)
6-3-4
Operation with 3 Wire Function of Terminal Block
7
*1
[STA]
8
*1
[STP]
9
*1
[FR]
A
COM
Input terminal
ON
OFF
OFF
ON
STA
STP
F/R
Forward
rotation
Output
speed
Reverse
rotation
Содержание RX - 2
Страница 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Страница 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Страница 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Страница 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Страница 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Страница 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Страница 919: ......