5-16 User Parameters
5
Ope
rati
ng Func
tions
• First set the Vibration Frequency 1 (Pn2B). Then reduce the setting of Pn2C if torque saturation
occurs or increase the setting of Pn2C to increase operation speed. Normally, use a setting of 0.
• Other than the setting range, the following restriction also applies: 10.0 Hz
−
Pn2B
≤
Pn2C
≤
Pn2B.
• Refer to
on page 7-35 for more information.
• Use this parameter to set the vibration frequency 2 for damping control to suppress vibration at the
end of the load.
• Measure the frequency at the end of the load and make the setting in units of 0.1 Hz.
• Setting frequency: 10.0 to 200.0 Hz. The function will be disabled if the setting is 0 to 9.9 Hz.
• Refer to
on page 7-35 for more information.
• First set the Vibration Frequency 2 (Pn2D). Then reduce the setting of Pn2E if torque saturation
occurs or increase the setting of Pn2E to increase operation speed. Normally, use a setting of 0.
• Other than the setting range, the following restriction also applies: 10.0 Hz
−
Pn2D
≤
Pn2E
≤
Pn2D
• Refer to
on page 7-35 for more information.
Pn2C
Vibration Filter 1 Setting
Setting range
−
200 to 2000
Unit
0.1 Hz
Default setting
0
Power OFF
→
ON
---
Pn2D
Vibration Frequency 2
Setting range
0 to 2000
Unit
0.1 Hz
Default setting
0
Power OFF
→
ON
---
Pn2E
Vibration Filter 2 Setting
Setting range
−
200 to 2000
Unit
0.1 Hz
Default setting
0
Power OFF
→
ON
---
Position
Position
Position
Содержание R88D-GT series
Страница 20: ...18 Table of Contents ...
Страница 234: ...3 133 3 8 Reactor Specifications 3 Specifications ...
Страница 448: ...7 37 7 5 Manual Tuning 7 Adjustment Functions ...
Страница 474: ...8 25 8 5 Periodic Maintenance 8 Troubleshooting ...
Страница 475: ...Chapter 9 Appendix 9 1 Connection Examples 9 1 9 2 Parameter Tables 9 11 ...
Страница 509: ......