4-39
4-3 Wiring Conforming to EMC Directives
4
System Design
Surge Suppressors
• Install surge suppressors for loads that have induction coils, such as relays, solenoids, brakes,
clutches, etc.
• The following table shows the types of surge suppressors and recommended products.
• Thyristors and varistors are made by the following companies. Refer to manufacturers'
documentation for details on these components.
Thyristors: Ishizuka Electronics Co.
Varistors: Ishizuka Electronics Co., Matsushita Electric Industrial Co.
Contactors
• Select contactors based on the circuit's inrush current and the maximum momentary phase
current.
• The Servo Drive inrush current is covered in the preceding explanation of no-fuse breaker
selection, and the maximum momentary phase current is approximately twice the rated current.
• The following table shows the recommended contactors.
Type
Features
Recommended products
Diode
Diodes are used for relatively small loads
when the reset time is not an issue, such
as relays.
At power shutoff the surge voltage is the
lowest, but the rest time takes longer.
Used for 24/48-VDC systems.
Use a fast-recovery diode with a short re-
verse recovery time (e.g. RU2 of Sanken
Electric Co., Ltd.).
Thyristor or
varistor
Thyristors and varistors are used for loads
when induction coils are large, as in elec-
tromagnetic brakes, solenoids, etc., and
when reset time is an issue. The surge
voltage at power shutoff is approximately
1.5 times the varistor voltage.
Select the varistor voltage as follows:
24 VDC system: 39 V
100 VDC system: Varistor V. 200 V
100 VAC system: Varistor V. 270 V
200 VAC system: Varistor V. 470 V
Capacitor
+ resistor
The capacitor plus resistor combination is
used to absorb vibration in the surge at
power shutoff. The reset time can be
shortened by selecting the appropriate ca-
pacitance and resistance.
Okaya Electric Industries Co., Ltd.
XEB12002 0.2
μ
F - 120
Ω
XEB12003 0.3
μ
F - 120
Ω
Manufacturer
Model
Rated current
Coil voltage
OMRON
J7L-09-22200
11 A
200 VAC
J7L-12-22200
13 A
200 VAC
J7L-18-22200
18 A
200 VAC
J7L-32-22200
26 A
200 VAC
J7L-40-22200
35 A
200 VAC
J7L-50-22200
50 A
200 VAC
J7L-65-22200
65 A
200 VAC
J7L-75-22200
75 A
200 VAC
Содержание R88D-GT series
Страница 20: ...18 Table of Contents ...
Страница 234: ...3 133 3 8 Reactor Specifications 3 Specifications ...
Страница 448: ...7 37 7 5 Manual Tuning 7 Adjustment Functions ...
Страница 474: ...8 25 8 5 Periodic Maintenance 8 Troubleshooting ...
Страница 475: ...Chapter 9 Appendix 9 1 Connection Examples 9 1 9 2 Parameter Tables 9 11 ...
Страница 509: ......