A - 145
Appendices
AC Servomotors/Servo Drives 1S-series with Built-in EtherCAT® Communications User’s Manual (I586)
A-4 Sys
m
ac Error S
ta
tus C
o
d
es
A
A-4
-2 Err
or De
scriptions
Event name
FSoE Slave Address Error
Event code
388B0000 hex
Description
Safety process data communications were not established with the Safety CPU Unit because of an incor-
rect FSoE slave address.
Source
EtherCAT Master Function Mod-
ule
Source details
Slave
Detection
timing
When establish-
ing FSoE com-
munications
Error
attributes
Level
Minor fault
Recovery
Error reset
(after resetting
slave errors)
Log category
System log
Effects
User program
Continues.
Operation
Power drive circuit is OFF
Indicators
EtherCAT NET RUN
EtherCAT NET ERR
EtherCAT LINK/ACT
---
---
---
System
-defined
variables
Variable
Data type
Name
None
None
None
Cause and
correction
Assumed cause
Correction
Prevention
The setting of the FSoE slave
address in the safety process
data communications settings is
different from the setting in the
Unit
Perform the FSoE Slave Address
Clear for the Servo Drive.
If you use a Servo Drive for which
safety process data communica-
tions were previously established
in another system, perform the
FSoE Slave Address Clear before
you use the Servo Drive.
Attached
information
None
Precautions/
Remarks
AL status code: -, Error No.: 7002 hex
Event name
FPGA WDT Error
Event code
48080000 hex
Description
An FPGA error was detected.
Source
EtherCAT Master Function Mod-
ule
Source details
Slave
Detection
timing
Continuously
Error
attributes
Level
Minor fault
Recovery
Error reset
(after cycling
slave power)
Log category
System log
Effects
User program
Continues.
Operation
Power drive circuit is OFF
Indicators
EtherCAT NET RUN
EtherCAT NET ERR
EtherCAT LINK/ACT
---
---
---
System
-defined
variables
Variable
Data type
Name
None
None
None
Cause and
correction
Assumed cause
Correction
Prevention
False detection due to a data
read error that was caused by
excessive noise
If this event does not occur after
you cycled the power supply, use
the product continuously. It is sup-
posed that a temporary error
occurred due to a read error. If this
event occurs again, the hardware
is faulty. Replace the Servo Drive.
If the normal operation can restart
after you cycled the power supply,
consider noise countermeasures.
There may be excessive noise
around the Servo Drive.
Hardware failure
Attached
information
Attached information 1: System information
Precautions/
Remarks
AL status code: -, Error No.: 3500 hex
Содержание R88D-1SN01H-ECT
Страница 17: ...15 CONTENTS AC Servomotors Servo Drives 1S series with Built in EtherCAT Communications User s Manual I586...
Страница 266: ...3 Specifications 3 102 AC Servomotors Servo Drives 1S series with Built in EtherCAT Communications User s Manual I586...
Страница 430: ...8 Safety Function 8 16 AC Servomotors Servo Drives 1S series with Built in EtherCAT Communications User s Manual I586...
Страница 568: ...10 Operation 10 10 AC Servomotors Servo Drives 1S series with Built in EtherCAT Communications User s Manual I586...
Страница 822: ...Appendices A 174 AC Servomotors Servo Drives 1S series with Built in EtherCAT Communications User s Manual I586...
Страница 823: ...AC Servomotors Servo Drives 1S series with Built in EtherCAT Communications User s Manual I586 I 1 I Index...
Страница 826: ...I 4 AC Servomotors Servo Drives 1S series with Built in EtherCAT Communications User s Manual I586 Appendices...
Страница 827: ......