
A
Troubleshooting
A-73
2.3.3
I/O
Symptom
Possible cause
Check items
Corrective action
1
The command does not
work even when the
dedicated input signal is
supplied.
• No 24 V DC is supplied.
• Check the I/O interface
connector stop signal and
24V-power supply
connections.
• Check DI06 (stop) on the
"MONITOR" screen displayed
on the programming box.
• Supply 24 V DC.
• A problem in signal
connection occurred.
• Check the I/O interface
connector wiring.
• Correct the I/O interface
connector wiring.
• An alarm occurred.
• Connect the programming box
and check the alarm by using
self-diagnosis.
• Check the 7-segment LED
display on the front of the
controller.
• Check the cause from the
alarm information.
• Take the corrective action.
2
The dedicated output
signal is not output.
• No 24 V DC is supplied.
• Check the I/O interface
connector 24V-power supply
connections.
• Check DI04 on the
"MONITOR" screen displayed
on the programming box.
• Supply 24 V DC.
• A problem in signal
connection occurred.
• Check the I/O interface
connector wiring.
• Correct the I/O interface
connector wiring.
• An alarm occurred.
• Connect the programming box
and check the alarm by using
self-diagnosis.
• Check the 7-segment LED
display on the front of the
controller.
• Check the cause from the
alarm information.
• Take the corrective action.
3
The general-purpose I/O
signal is not output.
• No 24 V DC is supplied.
• Check the I/O interface
connector 24V-power supply
connections.
• Check DI04 on the
"MONITOR" screen displayed
on the programming box.
• Check the I/O interface
24V-power supply
connection.
• Supply 24 V DC.
• A problem in signal
connection occurred.
• Check the I/O interface
connector wiring.
• Correct the I/O interface
connector wiring.
• A problem in I/O interface
setting occurred.
• Check the ID setting of the
I/O interface.
• Correct the ID setting of the
I/O interface.
• An alarm occurred.
• Connect the programming box
and check the alarm by using
self-diagnosis.
• Check the 7-segment LED
display on the front of the
controller.
• Check the cause from the
alarm information.
• Take the corrective action.
Содержание R6YXC1000
Страница 1: ...7 6HULHV DW 1R 1 5 5RERW RQWUROOHU 86 5 6 0 18 6 5 5RERWV 5 6HULHV...
Страница 2: ......
Страница 10: ......
Страница 40: ......
Страница 42: ......
Страница 46: ......
Страница 48: ......
Страница 54: ......
Страница 56: ......
Страница 64: ......
Страница 80: ......
Страница 82: ......
Страница 102: ......
Страница 108: ......
Страница 110: ......
Страница 136: ......
Страница 168: ......
Страница 170: ......
Страница 174: ...8 Periodic inspection 8 4...
Страница 176: ......
Страница 182: ......
Страница 256: ......
Страница 258: ......
Страница 259: ......
Страница 260: ...DW 1R 1 XWKRUL HG LVWULEXWRU 3ULQWHG LQ XURSH...