SIEPCYEUOQ2V01A Q2V Technical Manual
691
■
n8-76: Id Switching Filter Time
No.
(Hex.)
Name
Description
Default
(Range)
n8-76
(05CD)
Expert
Id Switching Filter Time
Sets the filter time constant for the d-axis current reference. Usually it is not necessary to change
this setting.
200 ms
(0 - 5000)
■
n8-77: Hvy Load Iq Level
No.
(Hex.)
Name
Description
Default
(Range)
n8-77
(05CE)
Expert
Hvy Load Iq Level
Set
n8-49 [Heavy Load Id Current]
to the percentage of load current (q-axis current) that you will
apply, where
E5-03 [PM Mot Rated Current (FLA)] = a setting value of 100%
.
90%
(0 - 255%)
Note:
The change is linear between
n8-75 [Mid Load Iq Level (Low)]
and
n8-77
and the level of the pull-in current from
n8-78 [Mid Load Id
Current]
to
n8-49 [Heavy Load Id Current]
.
■
n8-78: Mid Load Id Current
No.
(Hex.)
Name
Description
Default
(Range)
n8-78
(05F4)
RUN
Expert
Mid Load Id Current
Sets the level of the pull-in current as a percentage, where
E5-03 [PM Mot Rated Current (FLA)]
= 100%
.
0%
(0 - 255%)
■
n8-79: Pull-In Curr@Deceleration
No.
(Hex.)
Name
Description
Default
(Range)
n8-79
(05FE)
Pull-In Curr@Deceleration
Sets the pull-in current that can flow during deceleration as a percentage of the
E5-03 [PM Mot
Rated Current (FLA)]
.
50%
(0 - 200%)
If overcurrent occurs during deceleration, slowly decrease the setting in 5% increments.
Note:
When
n8-79 = 0
, the drive will use the value set in
n8-51 [Ac/Dec Pull-In Current]
.
■
n8-84: Polarity Det Current
No.
(Hex.)
Name
Description
Default
(Range)
n8-84
(02D3)
Expert
Polarity Det Current
Sets the current that the drive uses to estimate the initial motor magnetic pole as a percentage
where
E5-03 [PM Mot Rated Current (FLA)] = 100%
.
100%
(0 - 150%)
WARNING!
Sudden Movement Hazard. Make sure that the polarity is correct before you send a Run command. If the drive
incorrectly detects the polarity, the drive can rotate in the direction opposite of the Run command and cause serious injury or
death.
When you use a Yaskawa motor, check the motor nameplate for an
“
Si
”
value and set this parameter ≥ "Si × 2".
Consult the motor manufacturer for information about maximum setting values.
Find the Polarity of Magnetic Poles
When you start operation, the drive estimates the magnetic poles and finds the polarity of the magnetic poles.
Use
U6-57 [n8-84: PoleDis IdDifVal]
to make sure that the magnetic pole estimate was correct.
When you do High Frequency Injection Auto-Tuning, the drive automatically sets
n8-84
.
■
n8-87: O/P VoltLim Method
No.
(Hex.)
Name
Description
Default
(Range)
n8-87
(02BC)
O/P VoltLim Method
Sets the method of output voltage limit. If there is vibration in the constant output range, set
Feedforward Method. Usually it is not necessary to change this setting.
0
(0, 1)
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Содержание Q2V Series
Страница 2: ...This Page Intentionally Blank 2 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 12: ...12 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 18: ...i 2 Legal Information 18 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 26: ...1 2 Features and Advantages of Control Methods 26 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 38: ...2 8 Installation Methods 38 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 70: ...3 3 Main Circuit Wiring 70 SIEPCYEUOQ2V01A Q2V Technical Manual Models B006 B012...
Страница 102: ...3 17 Motor Application Precautions 102 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 138: ...4 12 Test Run Checklist 138 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 143: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 143 EU Declaration of Conformity...
Страница 144: ...5 2 European Standards 144 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 145: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 145...
Страница 146: ...5 2 European Standards 146 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 266: ...7 10 Troubleshooting Without Fault Display 266 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 284: ...8 6 Storage Guidelines 284 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 312: ...10 10 Peripheral Devices and Options 312 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 430: ...11 21 Parameters Changed by PM Motor Code Selection 430 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 731: ...SIEPCYEUOQ2V01A Q2V Technical Manual 731 Z Z pulse Auto Tuning 125...
Страница 733: ...SIEPCYEUOQ2V01A Q2V Technical Manual 733...