662
SIEPCYEUOQ2V01A Q2V Technical Manual
Figure 12.126 Undertorque Detection Time Chart
Note:
The drive applies a hysteresis of approximately 10% of the drive rated output current or the motor rated torque to the overtorque/
undertorque detection function.
■
Mechanical Weakening Detection
The Mechanical Weakening Detection function detects the mechanical weakening of a machine that can cause
overtorque or undertorque because of motor speed and total drive operation time.
The drive activates the function if the drive total operation time is longer than the time set in
L6-11 [MechFatigue
Hold Off Time]
. You can use
U4-01 [Cumulative OpeTime]
to monitor the total operation time.
Parameter Settings
If overtorque or undertorque occur during the speed range set in
L6-08 [MechF Enable]
and
L6-09 [MechFatigue
Speed Detect Level]
for the length of time set in
L6-10 [MechFatigue Delay Time]
, the drive will detect
Mechanical Weakening. The drive uses
L6-01 to L6-03
to detect
oL5 [Mechanical Weakening Detection 1]
or
UL5
[Mechanical Weakening Detection 2]
. Parameter
L6-08
sets the operation after detection.
Set the terminal that outputs the fault in
H2-01 to H2-03 [MFDO Function Select]
.
Table 12.54 Mechanical Weakening Detection Settings Parameters
Configuration Parameter
Mechanical Deterioration Detection
MFDO Function Select
•
Terminal NO-CM
•
Terminal DO1-O1C
•
Terminal DO2-O2C
H2-01, H2-02, and H2-03 = 66
Operation Selection after Detection
L6-08
Detection Start Time
L6-11
Speed Range
Detection Criteria
L6-08
Detection Level
L6-09
Detection Time
L6-10
Overtorque
Detection Criteria
L6-01
Detection Level
L6-02
Detection Time
L6-03
■
L6-01: Trq Det1 Select
No.
(Hex.)
Name
Description
Default
(Range)
L6-01
(04A1)
Trq Det1 Select
Enables overtorque and undertorque detection and the operation of drives (operation status) after
detection.
0
(0, 1)
The drive detects overtorque if the motor current or output torque is more than the level set in
L6-02 [Trq Det1
Level]
for the length of time set in
L6-03 [Trq Det1 Time]
. The drive detects undertorque if the motor current or
output torque is less than the level set in
L6-02
for the length the time set in
L6-03
.
0 : Disabled
The drive will not detect overtorque or undertorque.
1 : Enabled
The behavior is adjusted using parameters
L6-50 [Trq Det1 Type]
,
L6-51 [Trq Det1 Action]
, and
L6-52 [Trq Det1
Condition]
.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Содержание Q2V Series
Страница 2: ...This Page Intentionally Blank 2 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 12: ...12 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 18: ...i 2 Legal Information 18 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 26: ...1 2 Features and Advantages of Control Methods 26 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 38: ...2 8 Installation Methods 38 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 70: ...3 3 Main Circuit Wiring 70 SIEPCYEUOQ2V01A Q2V Technical Manual Models B006 B012...
Страница 102: ...3 17 Motor Application Precautions 102 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 138: ...4 12 Test Run Checklist 138 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 143: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 143 EU Declaration of Conformity...
Страница 144: ...5 2 European Standards 144 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 145: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 145...
Страница 146: ...5 2 European Standards 146 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 266: ...7 10 Troubleshooting Without Fault Display 266 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 284: ...8 6 Storage Guidelines 284 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 312: ...10 10 Peripheral Devices and Options 312 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 430: ...11 21 Parameters Changed by PM Motor Code Selection 430 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 731: ...SIEPCYEUOQ2V01A Q2V Technical Manual 731 Z Z pulse Auto Tuning 125...
Страница 733: ...SIEPCYEUOQ2V01A Q2V Technical Manual 733...