SIEPCYEUOQ2V01A Q2V Technical Manual
■
L3-22: StallP@Acc Deceleration Time
No.
(Hex.)
Name
Description
Default
(Range)
L3-22
(04F9)
StallP@Acc Deceleration
Time
Sets the momentary deceleration time that the drive will use when it tries to accelerate a PM
motor and detected motor stalls. This function is applicable when
L3-01 = 2 [StallP Mode@Accel
= General Purpose]
.
0.0 s
(0.0 - 6000.0 s)
Set this parameter to 0.0 s to disable this function. The drive will decelerates in the deceleration time applicable at
the time when a motor stall occurs.
■
L3-23: CHP Stall P Selection
No.
(Hex.)
Name
Description
Default
(Range)
L3-23
(04FD)
CHP Stall P Selection
Sets the function to automatically decrease the Stall Prevention Level during Run for constant
output ranges.
1
(1, 2)
1 : Level@L3-06
The drive uses the level set in
L3-06 [StallP Level@Run]
through the full speed range.
2 : Automatic Reduction
The drive decreases the Stall Prevention level during run in the constant power range. The lower limit is 40% of
L3-06
value.
■
L3-24: Acc@Rated Torque
No.
(Hex.)
Name
Description
Default
(Range)
L3-24
(046E)
Expert
Acc@Rated Torque
Sets the motor acceleration time to reach the maximum frequency at the motor rated torque for
stopped single-drive motors.
Determined by o2-04, C6-
01, E2-11, and E5-01
(0.001 - 10.000 s)
Set one of these parameters to enable L3-20:
•
L2-29 = 2 [KEB Method = Single KEB2 Ride-Thru]
•
L3-04 = 1 [StallP@Decel Enable = Enabled]
and
L3-50 = 1 [StallP@Decel Mode = Automatic Decel
Reduction]
•
L3-11 = 1 [Overvolt Supression Select = Enabled]
•
H1-xx = 42 or 43 [MFDI Function Select = KEB Thru2 NC or KEB Thru2 NO]
Note:
When Auto-Tuning changes the value of
E2-11 [Motor Rated Power (kW)]
, the drive will automatically set
this parameter
to the value
for a Yaskawa standard motor (4 poles). When you use a PM motor, the drive uses the value in
E5-01 [PM Mot Code Selection]
to
change
L3-24
.
■
L3-25: Load Inertia Ratio
No.
(Hex.)
Name
Description
Default
(Range)
L3-25
(046F)
Expert
Load Inertia Ratio
Sets the ratio between motor inertia and machine inertia.
1.0
(0.1 - 1000.0)
Set one of these parameters to enable L3-20:
•
L2-29 = 2 [KEB Method = Single KEB2 Ride-Thru]
•
L3-04 = 1 [StallP@Decel Enable = Enabled]
and
L3-50 = 1 [StallP@Decel Mode = Automatic Decel
Reduction]
•
L3-11 = 1 [Overvolt Supression Select = Enabled]
•
H1-xx = 42 or 43 [MFDI Function Select = KEB Thru2 NC or KEB Thru2 NO]
Note:
•
If you set this value incorrectly when
L2-29 = 1
,
H1-xx = 42 or 43
, or
L3-11 = 1
, it can cause large current ripples and
ov
[Overvoltage]
,
Uv1 [DC Bus Undervoltage]
, or
oC [Overcurrent]
faults.
•
KEB Tuning will automatically set this value.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Содержание Q2V Series
Страница 2: ...This Page Intentionally Blank 2 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 12: ...12 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 18: ...i 2 Legal Information 18 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 26: ...1 2 Features and Advantages of Control Methods 26 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 38: ...2 8 Installation Methods 38 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 70: ...3 3 Main Circuit Wiring 70 SIEPCYEUOQ2V01A Q2V Technical Manual Models B006 B012...
Страница 102: ...3 17 Motor Application Precautions 102 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 138: ...4 12 Test Run Checklist 138 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 143: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 143 EU Declaration of Conformity...
Страница 144: ...5 2 European Standards 144 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 145: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 145...
Страница 146: ...5 2 European Standards 146 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 266: ...7 10 Troubleshooting Without Fault Display 266 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 284: ...8 6 Storage Guidelines 284 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 312: ...10 10 Peripheral Devices and Options 312 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 430: ...11 21 Parameters Changed by PM Motor Code Selection 430 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 731: ...SIEPCYEUOQ2V01A Q2V Technical Manual 731 Z Z pulse Auto Tuning 125...
Страница 733: ...SIEPCYEUOQ2V01A Q2V Technical Manual 733...