SIEPCYEUOQ2V01A Q2V Technical Manual
641
Figure 12.114 KEB Function Wiring Example
■
Parameters for KEB Ride-Thru
This table shows the parameters that adjust the KEB Ride-Thru function. Parameter settings are different for the
different KEB methods set in
L2-29 [KEB Method]
.
Table 12.50 Parameters for KEB Ride-Thru
No.
Name
Configuring Settings
L2-29 [Kinetic Energy Backup Method]
0
1
2
3
C1-09
Fast Stop Time
•
If
ov [Overvoltage]
occurs during KEB deceleration, increase the setting value.
•
If
Uv1 [DC Bus Undervoltage]
occurs during KEB deceleration, decrease the
setting value.
x
-
-
-
C2-03
Jerk@Start of Decel
•
If
ov
occurs immediately after you start KEB deceleration, increase the setting
value.
•
If
Uv1
occurs immediately after you start KEB deceleration, decrease the
setting value.
x
-
x
x
L2-05
UV Detection Lvl (Uv1)
If
Uv1
occurs immediately after you start KEB deceleration, increase the setting
value to detect power loss more quickly.
x
x
x
x
L2-06
KEB Decel Time
•
Kinetic Energy Backup Decel Time
•
If
ov
or
Uv1
occur during KEB deceleration after KEB Tuning, set
L2-06
in
these conditions:
–
If
ov
occurs, increase the setting value
–
If
Uv1
occurs, decrease the setting value.
-
-
x
x
L2-07
KEB Accel Time
Sets the acceleration time to return to the frequency reference value before a
power loss, after you cancel the KEB operation. When
L2-07 = 0
, the drive uses
the standard acceleration times set in
C1-01, C1-03, C1-05, and C1-07
[Acceleration Time]
.
x
x
x
x
L2-08
Frq.Gain@KEB Start
•
If
ov
occurs immediately after you start operation, decrease the setting value.
•
If
Uv1
occurs immediately after you start operation, increase the setting value.
x
-
x
x
L2-10
Minimum KEB Time
•
With KEB Ride-Thru
There is
Uv1
because you set a digital input for KEB Ride-Thru and the device
that controls the input operated too slowly after power loss.
•
Without KEB Ride-Thru
If the DC bus voltage overshoots immediately after KEB Ride-Thru starts,
increase L2-10 to longer than the overshoot.
x
x
x
x
L2-11
KEB DC Volt Setpoint
•
Single Drive KEB Ride-Thru 2
Set to approximately 1.22 x input voltage.
•
Single Drive KEB Ride-Thru 1, System KEB Ride-Thru 1, or System KEB
Ride-Thru 2
Set to approximately 1.4 x input voltage.
x
x
x
x
L3-20
DCBus VoltAdj Gain
•
If
ov
or
Uv1
occurs at the start of deceleration when you use KEB operation,
increase this value in 0.1-unit increments.
•
If there is torque ripple during deceleration when you use KEB Ride-Thru,
decrease the value.
-
x
-
-
L3-21
OVSup Acc/Dec Gain
If there is large speed or current ripple, decrease the value in 0.05 unit increments.
Note:
If the setting value is too low, then the drive will have unsatisfactory DC bus
voltage control response. The drive can detect
ov
or
Uv1
.
-
x
-
-
Содержание Q2V Series
Страница 2: ...This Page Intentionally Blank 2 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 12: ...12 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 18: ...i 2 Legal Information 18 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 26: ...1 2 Features and Advantages of Control Methods 26 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 38: ...2 8 Installation Methods 38 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 70: ...3 3 Main Circuit Wiring 70 SIEPCYEUOQ2V01A Q2V Technical Manual Models B006 B012...
Страница 102: ...3 17 Motor Application Precautions 102 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 138: ...4 12 Test Run Checklist 138 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 143: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 143 EU Declaration of Conformity...
Страница 144: ...5 2 European Standards 144 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 145: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 145...
Страница 146: ...5 2 European Standards 146 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 266: ...7 10 Troubleshooting Without Fault Display 266 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 284: ...8 6 Storage Guidelines 284 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 312: ...10 10 Peripheral Devices and Options 312 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 430: ...11 21 Parameters Changed by PM Motor Code Selection 430 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 731: ...SIEPCYEUOQ2V01A Q2V Technical Manual 731 Z Z pulse Auto Tuning 125...