SIEPCYEUOQ2V01A Q2V Technical Manual
607
Note:
Refer to
“
L8-02: Overheat Alm Level on page 668
for more information.
■
4F: PreOHTimeLim
Setting Value
Function
Description
4F
PreOHTimeLim
The terminal activates when
L8-03 = 4 [Overheat Pre-Alarm Selection = Run@L8-19 Rate]
and
oH [Heatsink Overheat]
does
not clear after the drive decreases the frequency for 10 cycles.
Note:
Refer to
“
L8-03: Overheat Pre-Alarm Selection on page 668
for more information.
■
60: BrkTransFault
Setting Value
Function
Description
60
BrkTransFault
The terminal activates when the internal braking transistor overheats and the drive detects an
rr [Dynamic Braking Transistor
Fault]
fault.
■
61: BrkTransOH
Setting Value
Function
Description
61
BrkTransOH
The terminal activates when the braking resistor overheats and the drive detects an
rH [Braking Resistor Overheat]
fault.
The braking resistor overheats when the deceleration time is short and there is too much motor regeneration
energy.
■
63: Maintenance
Setting Value
Function
Description
63
Maintenance
The terminal activates when drive components are at their estimated maintenance period.
Tells the user about the maintenance period for these items:
•
IGBT
•
Cooling fan
•
Capacitor
•
Soft charge bypass relay
Note:
Refer to
“
Alarm Outputs for Maintenance Monitors
”
for more information.
■
65: WattH Pulse
Setting Value
Function
Description
65
WattH Pulse
Outputs the pulse that shows the watt hours.
Note:
Refer to
“
H2-06: kWH Out Unit Selection on page 589
”
for more information.
■
66: MechWeakDetect
Setting Value
Function
Description
66
MechWeakDetect
The terminal activates when the drive detects mechanical weakening.
Note:
Refer to
“
Mechanical Weakening Detection Function
”
for more information.
■
67: ModbusReg 1
Setting Value
Function
Description
67
ModbusReg 1
The terminal activates when the bit specified by
H2-08 [Mbus Reg1 Bit Select]
for the Modbus register address set with
H2-07
[Mbus Reg1 Address Select]
activates.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Содержание Q2V Series
Страница 2: ...This Page Intentionally Blank 2 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 12: ...12 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 18: ...i 2 Legal Information 18 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 26: ...1 2 Features and Advantages of Control Methods 26 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 38: ...2 8 Installation Methods 38 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 70: ...3 3 Main Circuit Wiring 70 SIEPCYEUOQ2V01A Q2V Technical Manual Models B006 B012...
Страница 102: ...3 17 Motor Application Precautions 102 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 138: ...4 12 Test Run Checklist 138 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 143: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 143 EU Declaration of Conformity...
Страница 144: ...5 2 European Standards 144 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 145: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 145...
Страница 146: ...5 2 European Standards 146 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 266: ...7 10 Troubleshooting Without Fault Display 266 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 284: ...8 6 Storage Guidelines 284 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 312: ...10 10 Peripheral Devices and Options 312 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 430: ...11 21 Parameters Changed by PM Motor Code Selection 430 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 731: ...SIEPCYEUOQ2V01A Q2V Technical Manual 731 Z Z pulse Auto Tuning 125...
Страница 733: ...SIEPCYEUOQ2V01A Q2V Technical Manual 733...