SIEPCYEUOQ2V01A Q2V Technical Manual
541
■
E5-24: PM BackEMF L-L Vrms (mV/rpm)
No.
(Hex.)
Name
Description
Default
(Range)
E5-24
(0353)
PM BackEMF L-L Vrms
(mV/rpm)
Sets the RMS value for PM motor line voltage.
200 V class: 100.0 mV/min
-
1
400 V class: 200.0 mV/min
-
1
(0.0 - 6500.0 mV/min
-1
)
Set this parameter when you use an SPM motor (SMRD-series, SMRA-Series Pico motor).
PM motor Auto-Tuning automatically sets this parameter to the value of [Back-EMF Voltage Constant (Ke)].
When
E5-01 = FFFF
, only set
E5-09 [PM BackEMF Vpeak (mV/(rad/ s))]
or
E5-24
as the induced voltage
constant.
Note:
When you set this parameter, also set
E5-09 = 0.0
. The drive will detect
oPE08 [Parameter Selection Error]
in these conditions:
•
E5-09 = 0.0
and
E5-24 = 0.0
•
E5-09 ≠ 0.0
and
E5-24 ≠ 0.0
■
E5-25: Polar Est Timeout
No.
(Hex.)
Name
Description
Default
(Range)
E5-25
(035E)
Expert
Polar Est Timeout
Sets the function that switches polarity for initial polarity estimation. Usually it is not necessary to
change this setting.
0
(0, 1)
When
“
Sd = 1
”
is shown on the motor nameplate or test report for Yaskawa motors, set this parameter to
1
.
0 : Disabled
1 : Enabled
◆
E9: SIMPLE VECTOR SETTINGS
E9 parameters
are used to configure induction motors, PM motors, and SynRM motors. Configure these
parameters only for derating torque applications in which a high level of responsiveness and accurate speed
control are not required.
E9 parameters
are automatically configured with values input by the Auto-Tuning process for motor parameter
settings.
E9 parameters
can be manually configured when the EZ Tuning process cannot be performed.
■
E9-01: Motor Type Selection
No.
(Hex.)
Name
Description
Default
(Range)
E9-01
(11E4)
Motor Type Selection
Sets the type of motor.
0
(0 to 2)
EZ Tuning automatically sets this parameter to the value of [Motor Type Selection].
0 : IM
1 : PM
2 : SynRM
■
E9-02: Maximum Speed
No.
(Hex.)
Name
Description
Default
(Range)
E9-02
(11E5)
Maximum Speed
Sets the maximum speed of the motor.
Determined by E9-01
(40.0 - 120.0 Hz)
Note:
The unit of measure changes when the setting of
o1-04 [V/f Pattern Unit for Display]
.
EZ Tuning automatically sets this parameter to the value of [Motor Max Revolutions].
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Содержание Q2V Series
Страница 2: ...This Page Intentionally Blank 2 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 12: ...12 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 18: ...i 2 Legal Information 18 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 26: ...1 2 Features and Advantages of Control Methods 26 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 38: ...2 8 Installation Methods 38 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 70: ...3 3 Main Circuit Wiring 70 SIEPCYEUOQ2V01A Q2V Technical Manual Models B006 B012...
Страница 102: ...3 17 Motor Application Precautions 102 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 138: ...4 12 Test Run Checklist 138 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 143: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 143 EU Declaration of Conformity...
Страница 144: ...5 2 European Standards 144 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 145: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 145...
Страница 146: ...5 2 European Standards 146 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 266: ...7 10 Troubleshooting Without Fault Display 266 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 284: ...8 6 Storage Guidelines 284 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 312: ...10 10 Peripheral Devices and Options 312 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 430: ...11 21 Parameters Changed by PM Motor Code Selection 430 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 731: ...SIEPCYEUOQ2V01A Q2V Technical Manual 731 Z Z pulse Auto Tuning 125...
Страница 733: ...SIEPCYEUOQ2V01A Q2V Technical Manual 733...