SIEPCYEUOQ2V01A Q2V Technical Manual
533
■
E2-04: Motor Pole Count
No.
(Hex.)
Name
Description
Default
(Range)
E2-04
(0311)
Motor Pole Count
Sets the number of motor poles.
4
(2 - 120)
Note:
•
When
A1-02 = 0 [Control Method = V/f Control]
, the maximum value is 120.
•
When
A1-02 = 2 [OLVector]
, the maximum value is 48.
Auto-Tuning automatically sets this parameter to the value of [Number of Motor Poles].
■
E2-05: Motor L-L Resistance
No.
(Hex.)
Name
Description
Default
(Range)
E2-05
(0312)
Motor L-L Resistance
Sets the line-to-line resistance for the motor stator windings.
Determined by o2-04, C6-
01
(0.000 - 65.000 Ω)
Note:
This value is the motor line-to-line resistance. Do not set this parameter with the single-phase resistance.
Auto-Tuning automatically sets this parameter. If you cannot do Auto-Tuning, use the test report from the motor
manufacturer to configure the settings. You can calculate the motor line-to-line resistance with one of these
formulas:
•
E-type insulation: [the resistance value (Ω) shown on the test report at 75 °C] × 0.92
•
B-type insulation: [the resistance value (Ω) shown on the test report at 75 °C] × 0.92
•
F-type insulation: [the resistance value (Ω) shown on the test report at 115 °C] × 0.87
■
E2-06: Motor Leak Inductance
No.
(Hex.)
Name
Description
Default
(Range)
E2-06
(0313)
Motor Leak Inductance
Sets the voltage drop from motor leakage inductance when the motor is operating at the rated
frequency and rated current. This value is a percentage of Motor Rated Voltage.
Determined by o2-04, C6-
01
(0.0 - 60.0%)
The drive automatically sets this parameter during Auto-Tuning.
Note:
The motor nameplate does not usually show the quantity of voltage drop. If you do not know the value of the motor leakage inductance,
contact the motor manufacturer to receive a copy of the motor test report.
■
E2-07: Mot Sat Coeff 1
No.
(Hex.)
Name
Description
Default
(Range)
E2-07
(0314)
Mot Sat Coeff 1
Sets the motor iron-core saturation coefficient at 50% of the magnetic flux.
0.50
(0.00 - 0.50)
The drive uses this coefficient when it operates with constant output. The drive uses this coefficient when it
operates the motor in the constant output range.
■
E2-08: Mot Sat Coeff 2
No.
(Hex.)
Name
Description
Default
(Range)
E2-08
(0315)
Mot Sat Coeff 2
Sets the motor iron-core saturation coefficient at 75% of the magnetic flux.
0.75
(E2-07 - 0.75)
The drive uses this coefficient when it operates with constant output. The drive uses this coefficient when it
operates the motor in the constant output range.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Содержание Q2V Series
Страница 2: ...This Page Intentionally Blank 2 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 12: ...12 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 18: ...i 2 Legal Information 18 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 26: ...1 2 Features and Advantages of Control Methods 26 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 38: ...2 8 Installation Methods 38 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 70: ...3 3 Main Circuit Wiring 70 SIEPCYEUOQ2V01A Q2V Technical Manual Models B006 B012...
Страница 102: ...3 17 Motor Application Precautions 102 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 138: ...4 12 Test Run Checklist 138 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 143: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 143 EU Declaration of Conformity...
Страница 144: ...5 2 European Standards 144 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 145: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 145...
Страница 146: ...5 2 European Standards 146 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 266: ...7 10 Troubleshooting Without Fault Display 266 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 284: ...8 6 Storage Guidelines 284 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 312: ...10 10 Peripheral Devices and Options 312 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 430: ...11 21 Parameters Changed by PM Motor Code Selection 430 SIEPCYEUOQ2V01A Q2V Technical Manual...
Страница 731: ...SIEPCYEUOQ2V01A Q2V Technical Manual 731 Z Z pulse Auto Tuning 125...
Страница 733: ...SIEPCYEUOQ2V01A Q2V Technical Manual 733...