8-42
8-5 Interface Monitor Setting Parameters
OMNUC G5-SERIES AC SERVOMOTOR AND SERVO DRIVE USER'S MANUAL
8
Parameters Details
Explanation of Set Values
Use this in combination with the Positioning Completion Range 1 (Pn431) to set the operation for
positioning completion output (INP: CN1 pin 39).
When Positioning Completion Hold Time (Pn433) is set to 0, hold time becomes infinite and ON
status is held until the next position command comes in.
General-purpose output timing is set by rotation speed r/min.
General-purpose output 1 (ZSP) will be turned ON when the speed of the motor is lower than the
setting of this parameter.
The setting of this parameter is valid for both forward and reverse direction regardless of the motor
rotation direction. This setting has a hysteresis of 10 r/min.
Pn432
Positioning Completion Condition Selection
Setting
range
0 to 3
Unit
−
Default
setting
0
Power OFF
and ON
−
Position
Full closing
Set
value
Explanation
0
Positioning completion output turns ON when the position error is within the Positioning
Completion Range 1 (Pn431).
1
Positioning completion output turns ON when the position error is within the Positioning
Completion Range 1 (Pn431) and there is no position command.
2
Positioning completion output turns ON when the zero speed detection signal is ON, the
position error is within the Positioning Completion Range 1 (Pn431), and there is no position
command.
3
Positioning completion output turns ON when the position error is within the Positioning
Completion Range 1 (Pn431) and there is no position command. The ON status will then be
held until the Positioning Completion Hold Time (Pn433) elapses. After that, an ON/OFF
decision will be made based on the position error at the time.
Pn433
Positioning Completion Hold Time
Setting
range
0 to 30,000
Unit
1 ms
Default
setting
Power OFF
and ON
−
Position
Full closing
Pn434
Zero Speed Detection
Setting
range
10 to 20,000
Unit
r/min
Default
setting
20
Power OFF
and ON
−
All
Speed
Reverse operation
OUTM1
ON
(Pn434
+
10)r/min
Forward operation
(Pn434
−
10)r/min
Содержание OMNUC G5
Страница 26: ......
Страница 82: ......
Страница 222: ......
Страница 266: ......
Страница 356: ......
Страница 364: ......
Страница 430: ......
Страница 542: ......
Страница 543: ...I OMNUC G5 SERIES AC SERVOMOTOR AND SERVO DRIVE USER S MANUAL Index...
Страница 548: ...Index 5 Index I...
Страница 549: ......