8-20
8-3 Vibration Suppression Parameters
OMNUC G5-SERIES AC SERVOMOTOR AND SERVO DRIVE USER'S MANUAL
8
Parameters Details
8-3 Vibration Suppression Parameters
Explanation of Set Values
Set the operation of the adaptive filter.
The adaptive filter is normally disabled in the TORQUE CONTROL mode.
Set the frequency of resonance suppression notch filter 1.
The notch filter function will be disabled if this parameter is set to 5,000.
Set the width of resonance suppression notch filter 1 to one of 20 levels.
Increasing the setting widens the notch width. Normally, use the default set value.
Set the notch depth of resonance suppression notch filter 1.
Increasing the setting will shorten the notch depth and the phase lag.
Set the notch frequency of resonance suppression notch filter 2.
The notch filter function will be disabled if this parameter is set to 5,000.
Select the notch width of resonance suppression notch filter 2.
Increasing the setting widens the notch width. Normally, use the default set value.
Pn200
Adaptive Filter Selection
Setting
range
0 to 4
Unit
−
Default
setting
0
Power OFF
and ON
−
Position Speed Full closing
Set value
Explanation
0
Disabled. The current values are held for the parameters related to notch filters 3 and 4.
1
1 enabled.The parameter related to notch filter 3 is updated based on the applicable result.
2
2 enabled.The parameters related to notch filters 3 and 4 are updated based on the applicable result.
3
The resonance frequency is measured.The measurement result can be checked using CX-
Drive.The current values are held for the parameters related to notch filters 3 and 4.
4
Adaptive result is cleared.Parameters related to notch filters 3 and 4 are disabled and the adaptive result is cleared.
Pn201
Notch 1 Frequency Setting
Setting
range
50 to 5,000
Unit
Hz
Default
setting
5,000
Power OFF
and ON
−
All
Pn202
Notch 1 Width Setting
Setting
range
0 to 20
Unit
−
Default
setting
2
Power OFF
and ON
−
All
Pn203
Notch 1 Depth Setting
Setting
range
0 to 99
Unit
−
Default
setting
−
Power OFF
and ON
−
All
Pn204
Notch 2 Frequency Setting
Setting
range
50 to 5,000
Unit
Hz
Default
setting
5,000
Power OFF
and ON
−
All
Pn205
Notch 2 Width Setting
Setting
range
0 to 20
Unit
−
Default
setting
2
Power OFF
and ON
−
All
Содержание OMNUC G5
Страница 26: ......
Страница 82: ......
Страница 222: ......
Страница 266: ......
Страница 356: ......
Страница 364: ......
Страница 430: ......
Страница 542: ......
Страница 543: ...I OMNUC G5 SERIES AC SERVOMOTOR AND SERVO DRIVE USER S MANUAL Index...
Страница 548: ...Index 5 Index I...
Страница 549: ......