4 Installation and Wiring
4 - 42
NX-series CPU Unit Hardware User’s Manual (W535)
Rapid temperature changes can cause condensation to occur, resulting in malfunctioning due to
short-circuiting.
When there is a possibility of this occurring, take measures against condensation, such as leaving the
Controller power ON at night or installing a heater in the control panel to keep it warmer.
The Controller is tested for conformity with the sine wave vibration test method (IEC 60068-2-6) and the
shock test method (IEC 60068-2-27) of the Environmental Testing for Electrotechnical Products. It is
designed so that malfunctioning will not occur within the specifications for vibration and shock. If, how-
ever, the Controller is to be used in a location in which it will be directly subjected to regular vibration or
shock, then implement the following countermeasures:
• Separate the control panel from the source of the vibration or shock.
Or secure the Controller and the panel with rubber padding to prevent vibration.
• Make the building or the floor vibration-resistant.
• To prevent shock when other devices in the panel such as electromagnetic contactors operate,
secure either the source of the shock or the Controller with rubber padding.
Using the Controller in any of the following locations can cause defective contact with connectors and
corrosion of components. Implement countermeasures such as purging the air as required.
• In locations exposed to dust, dirt, salt, metal powder, soot, or organic solvents, use a panel with an
airtight structure. Be careful of temperature increases inside the panel.
• In locations exposed to corrosive gas, purge the air inside the panel to clear the gas and then pres-
surize the inside of the panel to prevent gas from entering from outside.
• In locations where flammable gas is present, either use an explosion-protected construction or do not
use the Controller.
4-5-2
Humidity
4-5-3
Vibration and Shock
4-5-4
Atmosphere
Moisture
absorber
Power ON
Control panel
Heater
Examples of Measures against Condensation
Controller
Содержание NX701-1620
Страница 11: ...9 Manual Structure NX series CPU Unit Hardware User s Manual W535...
Страница 46: ...Sections in this Manual 44 NX series CPU Unit Hardware User s Manual W535...
Страница 64: ...1 Introduction to NX series Controllers 1 18 NX series CPU Unit Hardware User s Manual W535...
Страница 72: ...2 System Configuration 2 8 NX series CPU Unit Hardware User s Manual W535...
Страница 90: ...3 Configuration Units 3 18 NX series CPU Unit Hardware User s Manual W535...
Страница 156: ...6 Inspection and Maintenance 6 14 NX series CPU Unit Hardware User s Manual W535...
Страница 163: ...I 1 I NX series CPU Unit Hardware User s Manual W535 Index...
Страница 166: ...I 4 NX series CPU Unit Hardware User s Manual W535 Index...
Страница 167: ......