5 - 17
5 Designing the Power Supply System
NX-series EtherCAT Coupler Unit User’s Manual (W519)
5-4
Selectin
g Ext
ernal Power Sup
p
lies
and
P
ro
tect
ive Devic
es
5
5-
4-2 Selecting t
he I/O P
o
wer Supplies
This section describes how to select the I/O power supplies for the EtherCAT Slave Terminal.
Use an SELV power supply that meets the following conditions for the I/O power supply.
• Has overcurrent protection.
• Has double or reinforced insulation between the input and output.
• Has an output voltage of 5 to 24 VDC (4.5 to 28.8 VDC).
*1. Use an output voltage that is appropriate for the I/O circuits of the NX Units and the connected external
devices.
Recommended Power Supplies: S8JX Series (manufactured by OMRON)
Use the calculation method that is described in
5-3 Designing the I/O Power Supply System
5-9 and calculate the total current consumption from the I/O power supply and the required power sup-
ply capacity of the I/O power supply.
Unlike the Unit power supply, it is not necessary to use only one I/O power supply to supply power to
the entire Slave Terminal.
Precautions for Correct Use
Consider the inrush current when the power supply is turned ON and select an I/O power sup-
ply with sufficient extra capacity. The inrush current when power is turned ON may prevent the
I/O power supply from operating correctly.
Consider the following items when you select protective devices (e.g., breakers and fuses) to protect
against short circuits and overcurrents in external circuits.
• Protective device specifications (fusing, detection characteristics, steady current, inrush current, etc.)
• Inrush current when power is turned ON
Overcurrent is the current that flows when an excessive load is connected and one of the following rat-
ings is exceeded.
• For the Unit power supply, the rating of the NX Unit power supply capacity or of the current capacity
of the power supply terminals
• For the I/O power supply, the rating of the maximum I/O power supply current or of the current capac-
ity of the power supply terminals
Refer to
3-1-2 EtherCAT Coupler Unit Specifications
on page 3-2 for the above ratings for the EtherCAT
Coupler Unit. For the ratings of NX-series power supply-related Units, refer to the
NX-series System
Units User’s Manual
(Cat. No. W523).
5-4-2
Selecting the I/O Power Supplies
Recommended Power Supplies
Calculating the Required Power Supply Capacity of the I/O Power
Supply
5-4-3
Selecting Protective Devices
Содержание NX-ECC201
Страница 38: ...Sections in this Manual 36 NX series EtherCAT Coupler Unit User s Manual W519...
Страница 46: ...1 EtherCAT Networks 1 8 NX series EtherCAT Coupler Unit User s Manual W519...
Страница 56: ...2 Features and System Configuration 2 10 NX series EtherCAT Coupler Unit User s Manual W519...
Страница 68: ...3 Specifications and Application Procedures 3 12 NX series EtherCAT Coupler Unit User s Manual W519...
Страница 82: ...4 Part Names and Functions 4 14 NX series EtherCAT Coupler Unit User s Manual W519...
Страница 100: ...5 Designing the Power Supply System 5 18 NX series EtherCAT Coupler Unit User s Manual W519...
Страница 214: ...9 Setting Up Slave Terminals 9 44 NX series EtherCAT Coupler Unit User s Manual W519...
Страница 254: ...11 EtherCAT Coupler Unit Functions 11 30 NX series EtherCAT Coupler Unit User s Manual W519...
Страница 278: ...12 Communications Performance 12 24 NX series EtherCAT Coupler Unit User s Manual W519...
Страница 340: ...14 Maintenance and Inspection 14 8 NX series EtherCAT Coupler Unit User s Manual W519...
Страница 400: ...Appendices A 60 NX series EtherCAT Coupler Unit User s Manual W519...
Страница 401: ...Index 1 NX series EtherCAT Coupler Unit User s Manual W519 I Index...
Страница 405: ......