10 - 25
10 Troubleshooting
NX-series Position Interface Units User’s Manual (W524)
10-
5 Unit
-sp
ecific
Tr
o
u
b
lesho
ot
-
in
g
10
1
0-5-1
Incr
ement
al Encoder Inp
ut Unit
s
10-5 Unit-specific Troubleshooting
This section describes errors and corrections for individual Units.
The following table shows the errors and corrections for Incremental Encoder Input Units.
10-5-1 Incremental Encoder Input Units
Error
Cause
Possible correction
No count pulses are
detected.
The input wiring is not correct. Check the wiring to the connected device.
I/O power is not being sup-
plied.
Check to see if the I/O power is supplied.
The I/O power supply voltage
is outside of the rated voltage
range.
Set the I/O power supply voltage so that it is within
the rated voltage range.
The setting of the Pulse Input
Method Setting is not correct.
Check the wiring to the connected device.
The Counter Enable bit in the
Encoder Counter Operation
Command parameter is set to
0 (counter disabled).
Set the Counter Enable bit in the Encoder Counter
Operation Command parameter to 1 (counter
enabled).
The gate control for the exter-
nal input is set to close the
gate.
Change the gate control signal for the external input
to open the gate.
The wiring to the connected
device is disconnected.
Check the wiring to the connected device.
There is a problem with the
connected device.
Replace the connected device.
Pulses are not counted
correctly.
The input pulse frequency
exceeds the maximum fre-
quency in the Unit specifica-
tions.
Set the input pulse frequency to within the allowed
range in the Unit specifications or within the maxi-
mum value for the mode.
The counter value is not
reset even when an
external input or phase-Z
reset input is received.
The input wiring is not correct. Check the wiring of the input.
The External Reset Enable bit
in the Encoder Counter Oper-
ation Command parameter is
set to 0 (disabled).
Set the External Reset Enable bit in the Encoder
Counter Operation Command parameter to 1
(enabled).
The Phase Z Reset Enable bit
in the Encoder Counter Oper-
ation Command parameter is
set to 0 (disabled).
Set the Phase Z Reset Enable bit in the Encoder
Counter Operation Command parameter to 1
(enabled).
The external input function is
not set to resetting.
Set the external input function to resetting.
Two or more functions other
than a general input were
selected for the external input
function selections.
Set only one of the external inputs to a function other
than a general input.
The external input logic is not
correct.
Check to see if the external input logic is correct.
Содержание NX-EC0112
Страница 13: ...11 Manual Structure NX series Position Interface Units User s Manual W524...
Страница 34: ...Revision History 32 NX series Position Interface Units User s Manual W524...
Страница 36: ...Sections in this Manual 34 NX series Position Interface Units User s Manual W524...
Страница 70: ...2 Specifications and Application Procedures 2 14 NX series Position Interface Units User s Manual W524...
Страница 78: ...3 Part Names and Functions 3 8 NX series Position Interface Units User s Manual W524...
Страница 108: ...4 Installation and Wiring 4 30 NX series Position Interface Units User s Manual W524 Unit...
Страница 114: ...4 Installation and Wiring 4 36 NX series Position Interface Units User s Manual W524...
Страница 126: ...5 I O Refreshing Methods 5 12 NX series Position Interface Units User s Manual W524...
Страница 340: ...8 Pulse Output Units 8 76 NX series Position Interface Units User s Manual W524...
Страница 462: ...Appendices A 74 NX series Position Interface Units User s Manual W524...
Страница 463: ...I 1 I NX series Position Interface Units User s Manual W524 Index...
Страница 466: ...I 4 NX series Position Interface Units User s Manual W524 Index...