6 - 77
6 Incremental Encoder Input Units
NX-series Position Interface Units User’s Manual (W524)
6-10 S
p
e
cificat
ion
s
6
6-
10-1 Gener
al S
pecifications
6-10 Specifications
This section provides the general specifications, pulse input specifications, and external input specifica-
tions of the Incremental Encoder Input Units.
The general specifications of the Incremental Encoder Input Unit are given below.
6-10-1 General Specifications
Item
Specifications
I/O interface
Push-in
Number of encoder input
channels
NX-EC0112, NX-EC0122, NX-EC0132, or NX-EC0142
: 1 channel
NX-EC0212 or NX-EC0222
: 2 channels
Input signals
Encoder inputs
External Inputs
: Phases A, B, and Z
: 3
*1
*1. The NX-EC0112, NX-EC0122, NX-EC0132, and NX-EC0142 each have three external inputs. You can select
from the following external input types: gate (1), latch (2), and reset (1). Refer to
on page 6-80 for the external input specifications.
Input form
NX-EC0112, NX-EC0122, NX-EC0212, or NX-EC0222
: Voltage input (24 VDC)
NX-EC0132 or NX-EC0142
:
Line receiver input
NX Unit power consump-
tion
NX-EC0112
NX-EC0122
NX-EC0132
NX-EC0142
NX-EC0212
NX-EC0222
: 0.85 W max.
: 0.95 W max.
: 0.95 W max.
: 1.05 W max.
: 0.85 W max.
: 0.95 W max.
I/O power supply voltage
20.4 to 28.8 VDC (24 VDC +20%/
−
15%)
Current consumption from
I/O power supply
NX-EC0112 or NX-EC0122
NX-EC0132 or NX-EC0142
NX-EC0212 or NX-EC0222
: No consumption
: 30 mA max.
*2
: No consumption
*2. If you use the 5-V power supply for an encoder, be sure to include that current too. Refer to
page A-2 for the method to convert a 5-V power supply current consumption to a 24-V power supply current
consumption.
I/O power supply method
NX bus
Weight
NX-EC0112 or NX-EC0122
NX-EC0132 or NX-EC0142
NX-EC0212 or NX-EC0222
: 70 g max.
: 130 g max.
: 70 g max.
Dimensions (Width ×
Height × Depth)
NX-EC0112, NX-EC0122, NX-EC0212, or NX-EC0222
: 12 × 100 × 71 mm
NX-EC0132 or NX-EC0142
: 24 × 100 × 71 mm
I/O data size
*3
*3. This is the default set value.
NX-EC0112 or NX-EC0122
NX-EC0132 or NX-EC0142
NX-EC0212 or NX-EC0222
: Inputs: 18 bytes,
Outputs: 4 bytes
: Inputs: 18 bytes,
Outputs: 4 bytes
: Inputs: 36 bytes,
Outputs: 8 bytes
Number of I/O entry map-
pings
*3
NX-EC0112 or NX-EC0122
NX-EC0132 or NX-EC0142
NX-EC0212 or NX-EC0222
: Inputs: 1, Outputs: 1
: Inputs: 1, Outputs: 1
: Inputs: 2, Outputs: 2
Содержание NX-EC0112
Страница 13: ...11 Manual Structure NX series Position Interface Units User s Manual W524...
Страница 34: ...Revision History 32 NX series Position Interface Units User s Manual W524...
Страница 36: ...Sections in this Manual 34 NX series Position Interface Units User s Manual W524...
Страница 70: ...2 Specifications and Application Procedures 2 14 NX series Position Interface Units User s Manual W524...
Страница 78: ...3 Part Names and Functions 3 8 NX series Position Interface Units User s Manual W524...
Страница 108: ...4 Installation and Wiring 4 30 NX series Position Interface Units User s Manual W524 Unit...
Страница 114: ...4 Installation and Wiring 4 36 NX series Position Interface Units User s Manual W524...
Страница 126: ...5 I O Refreshing Methods 5 12 NX series Position Interface Units User s Manual W524...
Страница 340: ...8 Pulse Output Units 8 76 NX series Position Interface Units User s Manual W524...
Страница 462: ...Appendices A 74 NX series Position Interface Units User s Manual W524...
Страница 463: ...I 1 I NX series Position Interface Units User s Manual W524 Index...
Страница 466: ...I 4 NX series Position Interface Units User s Manual W524 Index...