6 Incremental Encoder Input Units
6 - 50
NX-series Position Interface Units User’s Manual (W524)
2
Set the Counter Type, Maximum Counter Value, and Minimum Counter Value.
There are the following three pulse input methods for counters:
• Phase differential pulse input multiplication x2/4
• Pulse
+
direction inputs
• Up and down pulses
Use the Pulse Input Method parameter to change the input method.
There are two multiplications for the phase differential pulse inputs: x2 and x4.
The default setting is for x4 multiplication.
Connect the phase-A and phase-B2 phase differential pulse inputs to inputs A and B on the encoder.
Connect the reset input or latch input to input Z.
Change the Encoder Count Direction parameter in the Unit operation settings to change the count
direction.
on page 6-53 for information on changing the count direction.
x2 Multiplication
The counter operation is performed on the rising and falling edges of the phase-A signal.
The count is incremented if phase A is advanced from phase B and decremented if phase A is
delayed from phase B.
x4 Multiplication
This setting is used to increase the resolution of encoder input compared with multiplication x2.
The counter operation is performed on the rising and falling edges of the phase-A and phase-B sig-
nals.
The count is incremented if phase A is advanced from phase B and decremented if phase A is
delayed from phase B.
6-9-3
Pulse Input Method
Parameter name
Setting
Default
Remarks
Pulse Input Method
0: Not Supported
1: Phase differential pulse x2
2: Phase differential pulse x4
3: Pulse + direction
4: Up and down pulses
2
Changes are applied when the power sup-
ply to the NX Unit is turned ON or the NX
Unit is restarted.
Phase Differential Pulse Input Multiplication (x2/4)
Incremental
encoder
Input A
Input B
Input Z
Counter
A
B
Z
Reset input or
latch input
Содержание NX-EC0112
Страница 13: ...11 Manual Structure NX series Position Interface Units User s Manual W524...
Страница 34: ...Revision History 32 NX series Position Interface Units User s Manual W524...
Страница 36: ...Sections in this Manual 34 NX series Position Interface Units User s Manual W524...
Страница 70: ...2 Specifications and Application Procedures 2 14 NX series Position Interface Units User s Manual W524...
Страница 78: ...3 Part Names and Functions 3 8 NX series Position Interface Units User s Manual W524...
Страница 108: ...4 Installation and Wiring 4 30 NX series Position Interface Units User s Manual W524 Unit...
Страница 114: ...4 Installation and Wiring 4 36 NX series Position Interface Units User s Manual W524...
Страница 126: ...5 I O Refreshing Methods 5 12 NX series Position Interface Units User s Manual W524...
Страница 340: ...8 Pulse Output Units 8 76 NX series Position Interface Units User s Manual W524...
Страница 462: ...Appendices A 74 NX series Position Interface Units User s Manual W524...
Страница 463: ...I 1 I NX series Position Interface Units User s Manual W524 Index...
Страница 466: ...I 4 NX series Position Interface Units User s Manual W524 Index...