7
.
EtherNet/IP Connection Procedure
43
7.4. EtherNet/IP Communication Status Check
Confirm that the EtherNet/IP tag data links operate normally.
7.4.1. Checking the Connection Status
Check the connection status of the EtherNet/IP network.
1
Check with LED indicators on
Controller that the tag data links
operate normally.
The LED indicators in normal status
are as follows:
NET RUN: Green lit
NET ERR: Not lit
LINK/ACT: Yellow flashing
(Flashing while packets are being
sent and received.)
2
Check the LED indicators on Sensor
Controller.
The LED indicators in normal status
are as follows:
Red LED: Lighting
Green LED: Lighting
3
Select the
EtherNet/IP Device List
Tab.
4
Right-click and select
Monitor
from
the menu while Built-in EtherNet/IP
Port Settings is selected.
5
The Built-in EtherNet/IP Port
Settings Connection Monitor Tab
Page is displayed.
6
Select the
Status
Tab.
When the same check boxes are
selected as shown on the right, the
tag data links are normally in
operation.
Number: Node number
Blue: Connection normal